System Sensor SENS-RDR User Manual

Series, Sens-rdr sensitivity reader

Advertising
background image

onds, followed by a textual status indication (See Table
1). The reader will continue to display both results for
up to 30 minutes, or until the reader is reset.

Figure 1: Reader location on compatible System Sen-
sor smoke detectors

PUSH RECESSED
SWITCH WITH A
0.18 MAX.
DIAMETER TOOL

LED

RECESSED TEST SWITCH

POSITION SENS-RDR
AT AN ANGLE ON THE
OVAL AREA OR AT THE
CHAMBER OPENING
BY THE WORD “PAINT”
FOR 100-SERIES
DETECTORS, PLACE
THE SENS-RDR AT THE
SMALL CIRCULAR
INDENTATION NEAR
THE WORDS
DO NOT PAINT.

S0135-01

Figure 2: Position Reader on compatible System Sen-
sor smoke detectors

OR

S0227-00

NOTE: No further readings may be taken until the reader
is reset.
5. To measure the sensitivity of the next detector, reset the

reader by momentarily pressing the button. The LCD
will again display the word “READY”. Repeat steps 2
through 4, as necessary.

6. When finished, turn off the reader by pressing and hold-

ing the button for approximately 2 seconds until the
reader sounds.

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS

SENS-RDR
Sensitivity Reader

Series

D100-98-00

1

I56-1801-003

Before Using
The SENS-RDR sensitivity reader is a tool to measure the
sensitivity of i3 smoke detectors as well as 100 series con-
ventional smoke detectors (only models 2151 and 2151T
manufactured after April 2006). It CANNOT be used on the
200, 300, 400, 500, or 800 Series detectors.
NOTICE: This manual shall be left with the owner/user of
this equipment.
IMPORTANT: Use of the SENS-RDR is designed to “...assure
that each smoke detector is within its listed and marked
sensitivity range...” per NFPA 72. The SENS-RDR CANNOT,
however, initiate a detector/sensor alarm. Sensitivity testing
shall not be used as a substitute for smoke entry testing.
General Description
This battery-powered device is equipped with an infrared
optical interface for reading data automatically sent by the
smoke detector every ten seconds. The SENS-RDR decodes
the sensitivity and status data, and displays the informa-
tion on its LCD display.
The SENS-RDR may be used either as a hand-held device,
or with a standard threaded extension pole.
SENS-RDR Operation
1. Turn the reader on by pressing and holding the button

for approximately 2 seconds until the reader sounds.
The LCD will display the word “READY”. The “READY”
status indicates that the SENS-RDR is ready for accept-
ing data from an i

3

Series smoke detector.

2. Place the reader by the smoke detector being tested. Posi-

tion the reader at an angle on the oval area or at the cham-
ber opening by the word “PAINT” (See Figures 1 and 2).
A ledge and an anti-skid tip is provided on the reader to
maintain the reader in place while it reads the sensitivity.

3. Hold the reader in this position up to 10 seconds until

the reader sounds and the reader’s red LED illuminates.

NOTE: If the reader does not sound after 10 seconds,

verify that the reader is properly positioned, and the
LCD displays “READY”.

4. The LED and sounder indicate a valid reading is re-

ceived. The reader will automatically display two
results. The first is a percent per foot obscuration mea-
surement, which is displayed for approximately 3 sec-

Environmental Specifications
Operating Temperature Range:

32 to 120°F (0 to 49°C)

Storage Temperature Range (without batteries):

5 to 140°F (–15 to 60°C)

Operating Humidity Range:

10 to 90% RH non-condensing

I56-1

801-003

Advertising