System Sensor SSK451 User Manual

Page 3

Advertising
background image

D200-94-00

3

I56-1222-004

Temporal Sounder
The SSK451 accessory provides the option of sounding a
continuous or temporal pattern. The SSK451 will default to
sound in a continuous pattern. For a temporal pattern, wire
a field-installed jumper between terminals 2 and 3 on the
SSK451.
Mounting
Secure the SSK451 to a double-gang electrical box with the
four mounting screws provided.
Installation of the Optional Add-On PS24LO Strobe
This optional strobe can be purchased separately and is
easily added to the SSK451 accessory.
Figure 4:

RED TERMINAL

ON TOP

H0485-00

The PS24LO strobe will be mounted on top of the sounder,
on the left-hand side of the SSK451. Place one mounting
spacer between the SSK451 and the strobe adapter plate at
each screw attachment location. Attach the adapter plate,
spacer and SSK451 to the left-hand side of the double-gang
electrical outlet box with two mounting screws.
Slide the strobe terminals directly into the two slots in the
adapter plate and SSK451. The positive lug, which will be
colored red, must be installed into the top slot.
Grasp the catch area on the top of the strobe and squeeze
while applying inward force. Repeat for the catch area on
the bottom of the strobe.
Make sure the strobe catches fully engage into the slots in
the adapter plate and that no gap appears at the interface
between the strobe and adapter plate.

Optional SMOKE Strobe Lens
NOTE:
To meet the code requirements of certain jurisdictions,
an optional SMOKE lens can be purchased separately.
SMOKE lens, wall mount

PS12/24SLENSW

SMOKE lens, ceiling mount

PS12/24SLENSC

Please follow the instructions enclosed with the lens for
proper installation of the lens to the strobe.
Operation
The green “POWER” LED is illuminated whenever the duct
smoke detector is receiving power. With a DH100ACDC duct
smoke detector, the yellow “TROUBLE” LED is lit when the
sensor board is missing or the cover is removed for more
than twenty minutes. With a DH400 ACDC duct smoke de-
tector, the yellow “TROUBLE” LED is lit when the detector
head is missing. The red “ALARM” LED is displayed and
the horn will sound whenever the duct smoke detector is
in alarm.
No LEDs will be illuminated if the duct smoke detector is
not receiving power.
Test Function
Insert the key and turn clockwise to the “TEST” position.
The red LED will illuminate and the horn will sound. If an
optional strobe is installed, it will pulse.
Alarm Indication
With the key in the “TEST” position, some time will elapse
(40 seconds maximum), depending on the duct smoke de-
tector type, before the red alarm LED will illuminate and
the horn will sound.
Reset Function
Turn the key counterclockwise to the “RESET” position and
hold. The red alarm LED should turn off and the horn will
cease sounding. Then, turn the key back to the “ON” posi-
tion and remove.