System Sensor 1551B Plug-in Intelligent User Manual

System Sensor Equipment

Advertising
background image

D500-40-00

1

I56-1436-00

1551B Plug-in Intelligent

Ionization Sensors with Communications

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing
Please thoroughly read Guide for Proper Use of System
Smoke Detectors
(I56-407-XX), which provides detailed in-
formation on sensor spacing, placement, zoning, and spe-
cial applications. Copies of this manual are available from
System Sensor.

General Description

Models 1551B dual-chamber ionization intelligent sensors
utilize a state-of-the-art, unipolar sensing chamber. These
sensors are designed for use with duct housings DH500
and DH500AC/DC only, and to be used with compatible
control panels only. Connect sensors only to compatible
control units. (For installation in Canada, refer to CAN/
ULC-S524-M86, Standard for the Installation of Fire Alarm
Systems and CEC Part 1, Sec. 32.)

Two LED’s on each sensor light to provide a local 360

°

vis-

ibility of the sensor indication. The LED’s can be latched
on by code command from the panel for an alarm indica-
tion. The LED’s can also be unlatched to the normal condi-
tion by code command. Remote LED annunciator
capability is available as an optional accessory (Part No.
RA400).

Specifications
Diameter:

6.1 inches

(155 mm) installed in B501B

4.1 inches

(104 mm) installed in B501

Height:

2.3 inches

(58 mm)

Weight:

5 ounces

(150 gm)

Operating Temperature Range:

-10

°

to 60

°

C (14

°

to 140

°

F)

Note: Do not install where normal ambient temperatures extend beyond 0

°

to 49

°

C

(32

°

to 120

°

F)

Operating Humidity Range:

10% to 93% Relative Humidity

Mounting:

B501B flanged base
B501 flangeless base
B501 with RMK400 recessed mounting kit
B501BH Base with horn

Maximum Air Velocity:

1500 Ft./Min. (7.6 m/S)

Voltage Range:

15 to 32 VDC

Standby Current:

200

µ

A maximum @ 24 VDC (with no communication)

300

µ

A average maximum @ 24 VDC (with one communication every five seconds

and LED blink enabled)

LED Current:

6.5 mA @ 24 VDC

Wiring Guide
Model 1551B can be used with any one of a variety of plug-
in bases. Therefore, connect all wiring following the
installation instructions provided with the base that was
selected for use with the 1551B. As Figure 1 indicates,
bases are equipped with screw terminals for all
appropriate connections.

NOTE: All wiring must conform to applicable local codes,

ordinances, and regulations.

NOTE: Verify that all sensor bases are installed and that

the wiring polarity is correct at each base.

WARNING

Remove power from the loop before installing sensors.

1. Install sensors:

a. Verify that the sensor type matches the type written

on the label on the base.

b. Set the sensor to the desired address and record it on

the label on the base.

c. Place the sensor into the sensor base.
d. Rotate the sensor clockwise until it drops into place.
e. Continue rotating the sensor clockwise until it locks

in place.