System Sensor 2012H Photoelectronic User Manual

Page 3

Advertising
background image

D200-75-00

3

I56-1216-02

(If necessary, add an extension ring if the selected box does not have
adequate volume.) The power supply may be mounted remotely from
the detector.

• All wiring must be performed by a licensed electrician and installed in

compliance with the National Electrical Code, applicable local codes,
and any special requirements of the local authority having jurisdic-
tion.

• Use only the specified wire gauge. Maximum interconnect bus length

is 5,000 feet, #14 – 18 AWG cable.

• The detector includes a tamper-resist feature that, when activated,

requires a tool for detector removal. The following detector installa-
tion instructions include how to activate this feature.

Installation Instructions
1. Turn off power at main service panel.
2. Using wire connectors, attach either black wire from power supply to

black ac power wire. Attach other black wire from power supply to
white ac neutral wire.

3. Using wire connectors, connect red and gray power supply output

wires to the bus line wires supplying power to the remote detectors.
(See Figure 7.) Use color-coded bus wires.

4. Mount power supply to junction box and cover junction box with a 4″

square box cover, using box mounting screws.

5. Install a junction box where you plan to install the detector. (See type

and size for junction box above.)

6. Install bus line wires from power supply output to junction box. Use

#14-18 AWG wire only. See Figure 7 to determine maximum power bus
length for wire size and number of interconnected detectors.

7. Connect color-coded DC power bus wires to power input screw termi-

nals, located on detector back. If detectors will be interconnected or the
relay used, see following sections for specific installation instructions.

8. Remove detector from mounting bracket by turning the detector coun-

ter-clockwise and pulling the detector away from the bracket.

9. Remove small tab on mounting bracket to activate tamper-resist

feature, if desired. (To release a detector with this feature, push up
on locking tab with screwdriver while turning detector counterclock-
wise.)

10. Install mounting bracket to junction box.

11. Connect power wires to detector(s) as shown in Figure 8. Be sure to

tighten each terminal screw to secure wire in place. Tug wire to be sure
it is connected properly.

12. Attach smoke detector to mounting bracket by aligning arrows on side

of mounting bracket 1-inch to the right of the nib on the detector.
Rotate until the arrow and nib line up. (See Figure 8).

13. After installing all detectors, turn on power at the main service

panel.

14. Check for the green LED to flash about once every 30 to 40 seconds.

This means the detector is receiving power. Check all detectors.

NOTE: If the LED does not flash, power is not getting to the smoke detec-

tor. Check wiring. If LED still does not flash, return the smoke
detector to the manufacturer for repair.

15. Test each detector in the system. (See “Testing” below for more

detailed instructions.)

S0150-00

S0151-00

ALIGNMENT

ARROW

FOR TAMPER RESIST

BREAK OFF TAB HERE

MOUNTING

BRACKET

MOUNTING

SCREW

MOUNTING

SCREW

REMOVE

INSTALL

WHEN INSTALLING:

ALIGN ARROWS ON MOUNTING

BRACKET 1" TO THE RIGHT OF

THE NIB ON THE DETECTOR.

ROTATE UNTIL ARROW AND

NIB LINE UP.

Figure 8:

Dimensions
1-3/4” high
5-1/2” base dia.

Figure 7:

(–)

(+)

INTERCONNECT UP TO

12 DETECTORS

AUXILIARY

ALARM RELAY

12OVAC

A77-727-O1

12VDC POWER

SUPPLY

POWERS UP TO

16 DETECTORS

GRAY

RED

BLACK

BLACK

WIRE

GAUGE

14AWG

16AWG

18AWG

1 UNIT

5000

3735

2349

2 UNITS

2970

1867

1174

3 UNITS

1980

1245

783

4 UNITS

1485

933

587

5 UNITS

1188

747

469

6 UNITS

990

622

391

Maximum power bus length in feet, given number of units (maximum per bus) and wire size.

Maximum interconnect bus length: 5,000 FT., No. 14 – 18 AWG cable.

All wiring must conform to local electrical codes.

Relay contacts rating: 0.5A 30VDC; 0.5A 30VAC

7 UNITS

848

533

335

8 UNITS

742

466

293

9 UNITS

660

415

261

10 UNITS

594

373

234

11 UNITS

540

339

213

12 UNITS

495

311

195

GROUND

SIGNAL

(+) (–)

POWER INPUT

AUXILIARY

GROUND

SIGNAL

(+) (–)

POWER INPUT

AUXILIARY

GROUND

SIGNAL

(+) (–)

POWER INPUT

AUXILIARY

GROUND

SIGNAL

(+) (–)

POWER INPUT

AUXILIARY

GROUND

SIGNAL

(+) (–)

POWER INPUT

AUXILIARY

GROUND

SIGNAL

(+) (–)

POWER INPUT

AUXILIARY

Advertising