System Sensor 2100 and 2100T Photoelectronic User Manual

Page 2

Advertising
background image

D200-54-00

2

I56-710-05

Mounting
Each 2100 and 2100T detector is supplied with a mounting
bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 3-1/2 inch or 4 inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.

Tamper-resistance Feature
This detector includes a tamper-resistant feature that pre-
vents its removal from the bracket without the use of a tool.
To make the detector tamper-resistant, remove the smaller
tab by breaking it at the scribed line on the tamper-resistant
tab on the detector mounting bracket (see Figure 2), then
install the detector. To remove the detector from the bracket
once it has been made tamper resistant, use a small screw-
driver to depress the tamper-resistant tab, located in the
slot on the mounting bracket, and turn the detector coun-
terclockwise.

Wiring Installation Guidelines
All wiring must be installed in compliance with the Na-
tional Electrical Code, applicable local codes, and any spe-
cial requirements of the local authority having jurisdiction.
Proper wire gauges should be used. The conductors used to
connect smoke detectors to control panels and accessory
devices should be color-coded to reduce the likelihood of
wiring errors. Improper connections can prevent a system

Figure 1. Surface mounting of 2100 smoke detector

on 3-1/2-inch and 4-inch octagonal box:

D

O

N

O

T

P

A

IN

T

TAMPER SLOT
(DEPRESS TAB TO
REMOVE DETECTOR)

TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER-RESIST
FEATURE)

ALIGNMENT
ARROWS

A78-2563-00

from responding properly in the event of a fire.

The screw terminal block will accept 14 – 22 gauge wire.
For best system performance, all wiring should be installed
in separate grounded conduit; do not mix fire system wir-
ing in the same conduit as any other electrical wiring.
Twisted pair may be used to provide additional protection
against extraneous electrical interference.

Wire connections are made by stripping about 1/4 inch of
insulation from the end of the feed wire, inserting the wire
into the appropriate terminal, and tightening the screw to
secure the wire in place.

System Sensor smoke detectors are marked with a compat-
ibility identifier located as the last digit of a five digit code
stamped on the back of the product. Connect detectors only
to compatible control units as indicated in System Sensor’s
compatibility chart which contains a current list of UL
listed compatible control units and detectors. A copy of this
list is available from System Sensor upon request.

Installation

WARNING

Remove power from the control unit or initiating-device cir-
cuits before installing detectors.

1. Wire the plug-in screw terminal block per Figure 3 and

plug the terminal block into the detector.

2. Align the arrows on the detector with the arrows on the

mounting bracket.

3. Turn the detector clockwise in the mounting bracket un-

til it clicks into place.

4. After all detectors have been installed, apply power to

the control unit or initiating-device circuits.

5. Test the detector as described in the following para-

graph.

6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.