System Sensor 2112_24AT Photoelectronic User Manual

System Sensor Equipment

Advertising
background image

D200-82-00

1

I56-1237-01R

2112/24AT

Photoelectronic Smoke Detector with

Fixed Heat and Integral Temp-3 Sounder

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Specifications
Diameter:

5.5 inches (140 mm)

Height (including mounting bracket):

2.05 inches (52 mm)

Weight:

7.5 oz. (210 g)

Operating Temperature Range:

32

°

to 100

°

F (0

°

to 38

°

C)

Operating Humidity Range:

10% to 93% Relative Humidity, Noncondensing

Latching Alarm:

Reset by momentary power interruption

Audible Signal:

85 dBA minimum when in alarm or with supply polarity reversed

Heat Sensor:

135

°

F Fixed Temperature Electronic Thermistor

Electrical Ratings
System Voltage (nominal):

12 or 24 VDC

Minimum:

10 VDC

Maximum:

35 VDC

Maximum Ripple Voltage:

30% of nom. Voltage (peak to peak)

Standby Current:

50

µ

A maximum

Alarm Current:

49 mA typical, 60 mA max. at 12V
57 mA typical, 65 mA max. at 24V

Reset Voltage:

0.8 VDC minimum

Reset Time:

1.0 second maximum

Start-up Time:

30 seconds maximum (after 60 sec. reset)

EOL Relay:

A77-716B, 12/24 VDC

Alarm Initiation
Contact Rating, Resistive Load:

1A @ 30 VDC

Special Considerations:

Due to the built-in temporal pattern, use this detector only with a non-coded
power supply.

Figure 1. Wiring diagram for the 2112/24AT detector:

A78-2336-14

Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which pro-
vides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available at no charge from System Sensor.

NOTICE: This manual shall be left with the owner/user of
this equipment.

IMPORTANT: This detector must be tested and maintained
following NFPA 72 requirements. The detector should be
cleaned at least once a year.

IMPORTANT: OBSERVE POLARITY

As with all sounder models, polarity must be observed on the power connections.

OPTIONAL CLASS A WIRING

EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER

EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V

POWER

TO

DETECTORS

UL LISTED

COMPATIBLE

CONTROL

PANEL

INITIATING

LOOP

+

P

W

R

P

W

R

+
+

A
A

+
+

A
A

ALARM
CONTACT

ALARM
CONTACT

NOT USED

NOT USED