System Sensor 2151 and 2151T Low Profile Photoelectric Plug-in User Manual

Page 2

Advertising
background image

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer. Misuse or overuse of these products may have long term ad-
verse effects on the smoke detector. Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements.

D. Direct Heat Method (Hair Dryer of 1000-1500 watts) 2151T only

A hair dryer of 1000-1500 watts should be used to test the thermistors. Di-
rect the heat toward either of the two thermistors, holding the heat source
approximately 12 inches from the detector in order to avoid damaging
the plastic housing. The detector will reset only after it has had sufficient
time to cool. Make sure both thermistors are tested individually.

Notify the proper authorities that the system is back on line.
Detectors that fail these tests should be cleaned as described under MAIN-
TENANCE and retested. If the detectors still fail these tests, they should be
returned for repair.

LED Status

Indicators

Magnet Test

Marker

Test Magnet

Position

Test Magnet

Position

Magnet Test

Marker

SENS-RDR

Location

fIgURE 1. BOTTOM AND SIDE vIEWS ShOWINg POSITION Of
TEST MAgNET:

Sensor
Cover

Sensing
Chamber
Cover and
Screen

Cover
Removal
Tabs

Sensing
Chamber

Optional
Thermistors
(2151T only)

fIgURE 2:

C0892-01

C0145-03

SPECIAL NOTE REgARDINg SMOkE DETECTOR gUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.

CAUTION

Dust covers are an effective way to limit the entry of dust into smoke detector sens-
ing chambers. However, they may not completely prevent airborne dust particles
from entering the detector. Therefore, System Sensor recommends the removal
of detectors before beginning construction or other dust producing activity.
Be sure to remove the dust covers from any sensors that were left in place dur-
ing construction as part of returning the system to service.

CAUTION

Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.

D100-101-00

2

I56-2806-005R

©2010 System Sensor

System Sensor warrants its enclosed smoke detector to be free from defects in materials
and workmanship under normal use and service for a period of three years from date
of manufacture. System Sensor makes no other express warranty for this smoke detec-
tor. No agent, representative, dealer, or employee of the Company has the authority to
increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of the smoke
detector which is found to be defective in materials or workmanship under normal use
and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System Sensor, Repair

ThREE-YEAR LIMITED WARRANTY

Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a
note describing the malfunction and suspected cause of failure. The Company shall not
be obligated to repair or replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date of manufacture.
In no case shall the Company be liable for any consequential or incidental damages for
breach of this or any other Warranty, expressed or implied whatsoever, even if the loss
or damage is caused by the Company’s negligence or fault. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation
or exclusion may not apply to you. This Warranty gives you specific legal rights, and you
may also have other rights which vary from state to state.

Please refer to insert for the Limitations of Fire Alarm Systems

CLEANINg
Before removing the detector, notify the proper authorities that the smoke
detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.

1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each of the four removal

tabs that hold the cover in place.

3. Vacuum the screen carefully without removing it.

If further cleaning is required continue with Step 4, otherwise skip to
Step 7.

4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from

the sensing chamber.

6. Reinstall the chamber cover/screen assembly by sliding the edge over the

sensing chamber. Turn until it is firmly in place.

7. Replace the cover using the LEDs to align the cover and then gently

pushing it until it locks into place. Make sure that the thermistors do not
become bent under the cover on 2151T.

8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.

Advertising