d. Turn the sensor clockwise until it drops into place.
e. Continue turning the sensor clockwise until it locks

into place.

WARNING

Sensor will not detect smoke if dust cover is installed.

2. Tamper-proof feature:

The sensor bases include a tamper-proof feature that,
when activated, prevents removal of the sensor without
the use of a tool. See the installation instruction manual
for the sensor base for details in using this feature.

3. After all sensors have been installed, apply power to the

control unit.

4. Test all sensors per the TESTING section of this manual.

3

2

1

3

2

1

3

2

1

+

-

-

+

U.L. LISTED COMP

A

T

IBLE

CONTROL

P

ANEL

CLASS A OPTIONAL WIRING

REMOTE ANNUNCIATOR

+

-

CAUTION: Do not loop wire under terminal 1 or 2.
Break wire run to provide supervision of connections.

A78-1253-01

Figure 1. Wiring Diagram:

LED

LED

TEST MODULE

SOCKET

TEST

MAGNET

PAINTED

SURFACE

TEST

MAGNET

Figure 2. Views showing position of test magnet (model 2551T shown):

A78-1410-01

Testing
Before testing, notify the proper authorities that the smoke
sensor system is undergoing maintenance, and therefore
the system will temporarily be out of service. Disable the
zone or system undergoing maintenance to prevent un-
wanted alarms.
Sensors must be tested after installation and periodic main-
tenance. The sensor may be tested in the following ways:

A. Test Magnet (Model No. M02-04-00)

1. Place the magnet against the cover opposite the test

module socket to activate the test feature (see Figure 2).

2. The LEDs should latch on within 10 seconds indicat-

ing alarm and annunciating the panel.

B. Test Module (Model No. MOD400R)

The MOD400R is used with your DMM or voltmeter to
check the sensor sensitivity as described in the
MOD400R’s manual.