System Sensor 2412B, 2412THB, 2424, and 2424TH Direct Wire User Manual

System Sensor Equipment

Advertising
background image

D400-06-00 1 I56-286-05R

2412B, 2412THB, 2424, and 2424TH
Direct Wire Photoelectronic
Smoke Detectors

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

ww.systemsensor.com

Before Installing
Please thoroughly read the System Sensor manual A05-
1003, Applications Guide for System Smoke Detectors,
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available at no charge from System
Sensor. (For installation in Canada, refer to CAN/ULC-
S524, Standard for the Installation of Fire Alarm Systems
and CEC Part 1, Sec. 32.)

General Description
System Sensor 2412 and 2424 photoelectronic smoke detec-
tors utilize state-of-the-art, optical sensing chambers. These
detectors are designed to provide open area protection, and
to be used with compatible UL-listed 4-wire control panels
only. The 2412 applies to 12 volt panels and operates at
12VDC, and the 2424 applies to 24 volt panels and operates
at 24VDC. Operation and sensitivity can be tested in place.
Models 2412TH and 2424TH have the same specifications
as models 2412 and 2424, but in addition feature a built-in
fixed temperature (135°F) thermal detection unit.

Specifications
Diameter: 5.5 inches (14 cm)
Height: 3.19 inches (81 mm); Add 0.5 inches (1.3 cm) for thermal units
Weight: 0.7 lb (310 g)
Operating Temperature Range: 2412 and 2424 — 0°C to +49°C (32°F to 120°F)
2412TH and 2424TH — 0° to +38°C (32° to 100°F)
Operating Humidity Range: 10% to 93% Relative Humidity
Maximum Air Velocity: 3000 Ft./Min. (15 M/S)
Latching Alarm: Reset by momentary power interruption.
Electrical Ratings 2412 2424
System Voltage: 12 24

DC (4V Maximum Ripple)

Supply Voltage: 11.3 20

VDC Minimum

17 29

VDC Maximum

Reset Voltage: .73 .8

VDC Minimum

Standby Current: 120 120

µA Maximum

Alarm Currents: 35 21.3

mA Minimum

77 40.6

mA Maximum

The alarm and auxiliary relay operate within the specified voltage ratings.
Start-up Time: 34 34

S Maximum

EOL Relay: A77-716 A77-716
Reset Time: 0.3 0.3
Relay Contacts – resistive or inductive (60% power factor) load:
Form A: 2.0A @ 30VAC/DC
Form C:* 0.6A @ 110VDC; 2.0A @ 30VDC
1.0A @ 125VAC; 2.0A @ 30VAC
(*For Canadian installations, relay contact rating is 2.0A @ 30VAC/DC)

An LED on each detector lights to provide a local alarm indi-
cation. It flashes every ten seconds indicating that power
is applied to the detector. The LED lights continuously in
alarm. These detectors also have the latching alarm feature
that resets only by a momentary power interruption.

Each detector contains one set of Form A contacts for con-
nection to the alarm-initiating circuit, and one set of Form C
auxiliary contacts. Supervision of detector power is accom-
plished by installing a Power Supervisory End-of-Line Relay
Module (A77-716 Series) at the end of the detector power
loop. When power is applied to and through the detectors,
the EOL Power Supervisory Module is energized. Its relay
contacts close and provide a closed series circuit in the con-
trol panel’s alarm-initiating loop. A power failure or a break
in the detector power loop de-energizes the EOL Module.
The relay contacts open and trigger a trouble signal at the
control panel.

Advertising