System Sensor 5251B, 5251H, and 5251RB Intelligent Plug-In User Manual

System Sensor Equipment

Advertising
background image

SS-400-002

1 I56-3860-004R

5251B, 5251RB and 5251H
Intelligent Plug-In Temperature Sensors

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

BEFORE INSTALLING
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when
installed in compliance with the National Fire Protection Association (NFPA);
see NFPA 72.

Please read the system wiring and installation manual thoroughly. This man-
ual provides detailed information on sensor spacing, placement, zoning, and
special applications. Copies of these manuals are available from System Sen-
sor.
GENERAL DESCRIPTION
Models 5251B, 5251RB and 5251H are intelligent sensors that utilize a state-of-
the-art thermistor sensing circuit for fast response. These sensors are designed
to provide open area protection with 50 foot spacing capability as approved by
UL 521. Model 5251B is a fixed temperature sensor with 135°F fixed tempera-
ture alarm. Model 5251RB is a rate-of-rise temperature sensor with 135°F fixed
temperature alarm. Model 5251H is a high temperature sensor with 190°F
fixed temperature alarm.

Two LEDs on each sensor light to provide 360° visibility of the sensor indica-
tion. The LEDs can be latched ON by code command from the panel for an
alarm indication. The LEDs can also be unlatched to the normal condition
by code command. Remote LED annunciator capability is available as an op-
tional accessory (Part No. RA400Z/RA100Z).
Models 5251B, 5251RB and 5251H require compatible addressable commu-
nications to function properly. Connect these sensors to listed-compatible
control panels only.

NOTE: 5251RB Heat detectors are sold in the European Community for use
only in applications in conjunction with sprinkler systems. They must not be
used in Europe as part of an EN54 fire detection and alarm system
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes and the Authority Having Jurisdiction. Proper wire
gauges should be used. The installation wires should be color coded to limit
wiring mistakes and ease system troubleshooting. Improper connections will
prevent a system from responding properly in the event of a fire.
Remove power from the communication line before installing sensors.

1. Wire the sensor base (supplied separately) per the wiring diagram, see

Figure 1.

2. Set the desired address on the sensor address switches, see Figure 2.
3. Install the sensor into the sensor base. Push the sensor into the base

while turning it clockwise to secure it in place.

4. After all sensors have been installed, apply power to the control unit and

activate the communication line.

5. Test the sensor(s) as described in the TESTING section of this manual.

I56-3860-004R

SPECIFICATIONS
Diameter:

6.1 inches (155 mm) installed in B210LP; 4.1 inches (104 mm) installed in B501

Height:

2.0 inches (51 mm)

Weight:

4.8 ounces (137 gm)

Installation Temperatures:

–4°F to 100°F (–20°C to 38°C); 5251B and 5251RB; –4°F to 150°F (–20°C to 66°C); 5251H

Operating Humidity Range:

10% to 93% Relative Humidity Non-condensing

Mounting:

B210LP flanged base; B501 flangeless base; B501 with RMK400 recessed mounting kit

Voltage Range:

15 to 32 Volts DC Peak

Standby Current:

300 µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)

LED Current:

6.5 mA @ 24 VDC

Fixed Temperature Rating:

135°F (57°C); 5251B and 5251RB; 190°F (88°C); 5251H

Rate of Rise Detection:

Responds to greater than 15°F/min.; 5251RB

TAMPER RESISTANCE
The sensor bases have a tamper-resistant capability. When this capability is
enabled, sensors cannot be removed from the base without the use of a small
screwdriver or other similar tool. Refer to the sensor base installation instruc-
tion manual for details in using this capability.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.

All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors
offer maximum performance when tested and maintained in compliance with
NFPA 72. The sensor may be tested in the following ways:
A. TEST MAGNET (MODEL NO. M02-04)

1. Place the magnet against the cover in the magnet test area as shown

in Figure 3 to activate the test feature.

2. The LEDs should latch ON within 10 seconds, indicating alarm and

annunciating the panel.

3. Reset the detector at the system control panel.

B. DIRECT HEAT METHOD (HAIR DRyER OF 1000 – 1500 WATTS)

1. From the side of the detector, direct the heat toward the sensor. Hold

the heat source about 6 inches (15cm) away to prevent damage to the
cover during testing.

2. The LEDs on the detector should light when the temperature at the

detector reaches the alarm set point. If the LEDs fail to light, check
the power to the detector and the wiring in the detector base.

3. Reset the detector at the system control panel.

Detectors that fail these tests should be cleaned as described under MAIN-
TENANCE and retested. If the detectors still fail these tests they should be
returned for repair.
MAINTENANCE
NOTE: Before cleaning notify the proper authorities that the system is under-
going maintenance, and therefore the system will temporarily be out of ser-
vice. Disable the loop or system undergoing maintenance to prevent unwanted
alarms.
It is recommended that the sensor be removed from its mounting base for
easier cleaning and that sensors be cleaned at least once a year. Use a vacuum
cleaner to remove dust from the sensing chamber.

Advertising