B110LP Plug-in Detector Base

For use with the following smoke detectors:
IN US:

1151, 2151

IN CANADA:

1151A, 2151A

IN EUROPE:

1151E, 2151E

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which pro-
vides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available at no charge from System Sensor. (For
installation in Canada, please refer to CAN/ULC-S524,
Standard for the Installation of Fire Alarm Systems and CEC
Part 1, Sec. 32.)

NOTICE: This manual should be left with the owner/user
of this equipment.

IMPORTANT: The detector used with this base must be
tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.

Specifications
Base Diameter:

6.2 inches (157 mm)

Base Height:

0.95 inches (24 mm)

Weight:

0.3 lb. (137 g)

Mounting:

4-inch square box with or without plaster ring. Min. depth–1.5 inches
3-1/2-inch octagon box. Min. depth–1.5 inches

Operating Temperature Range: 0° to 49°C (32° to 120°F)
Operating Humidity Range:

10% to 93% Relative Humidity, Noncondensing

Electrical Ratings - includes base and detector
System Voltage:

12/24 VDC

Maximum Ripple Voltage:

4 Volts peak-to-peak

Start-up Capacitance:

0.02 µF Maximum

Standby Ratings:

8.5 VDC Minimum
35 VDC Maximum
120 µA Maximum

Alarm Ratings:

4.2 VDC Minimum at 10 mA
6.6 VDC Maximum at 100 mA
(Alarm current must be limited to 100 mA (130 mA for models 1151 and 2151) by the
control panel. If it is used, the RA400Z Remote Annunciator operates within the specified
detector alarm currents.)

Reset Voltage:

2.5 VDC Minimum

Reset Time:

0.3 Seconds Minimum

Start-up Time:

34.0 Seconds Maximum

General Description
The Model B110LP detector base is designed for use with
System Sensor models 2151 photoelectronic and 1151 ion-
ization detector heads. This two-wire base is equipped with
screw terminals for the connection of power, ground, and
an optional remote annunciator.

Mounting
The detector base mounts directly to 3-1/2 inch and 4-inch
octagon boxes and 4-inch square boxes, with or without
plaster rings. To mount the base, remove the decorative
ring by rotating it in either direction to unhook the snaps
before separating the ring from the base. Use the screws
supplied with the junction box to attach the base to the box
through the appropriate slots in the base (see Figure 1).
Position the decorative ring around the base and rotate it in
either direction until the ring snaps into place.