B116LP Plug-in Detector Base

For use with the following smoke detectors:
In US:

1151, 2151

In Canada:

1151A, 2151A

In Europe:

1151E, 2151E

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue,

St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which pro-
vides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available at no charge from System Sensor. (For
installation in Canada, please refer to CAN4-S524, Standard
for the Installation of Fire Alarm Systems and CEC Part 1,
Sec. 32.)

NOTICE: This manual should be left with the owner/user
of this equipment.

IMPORTANT: The detector used with this base must be

Specifications
Base Diameter:

6.2 inches (157 mm)

Base Height:

0.95 inches (24 mm)

Weight:

0.3 lb. (130 g)

Mounting:

4-inch square box with or without plaster ring. Min. Depth–1.5 inches
4-inch octagon box. Min. Depth–1.5 inches
3-1/2 inch-octagon box. Min. Depth–1.5 inches
50 mm box
60 mm box
70 mm box

Operating Temperature Range:

0° to +49°C (32° to 120°F) US and Canadian Installations
10° to 60°C (14° to 140°F) European Installations

Operating Humidity Range:

10% to 93% Relative Humidity

Electrical Ratings – includes base and detector
System Voltage:

24 VDC

Maximum Ripple Voltage:

4 Volts peak to peak

Start-up Capacitance:

0.02µF Maximum

Standby Ratings:

15 VDC Minimum
35 VDC Maximum
120 µA Maximum

Alarm Ratings:

8 V Minimum at 16 mA
12 V Maximum at 100 mA
(Alarm current MUST be limited to 100 mA maximum by the control panel.)

Relay Contact Ratings:
Resistive or Inductive (60% power factor) Load
Form C:*

2.0A @ 30 VAC/DC
0.6A @ 110 VDC
1.0A @ 125 VAC

Reset Voltage:

1.4 VDC Minimum

Reset Time:

0.3 Seconds Maximum

Start-up Time:

34.0 Seconds Maximum

*For Canadian installations relay contact ratings are 2.0A @ 30 VAC/DC.

tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.

General Description
The model B116LP plug-in detector base is used with
System Sensor model 1151, 1151A, and 1151E ionization
detector heads and model 2151, 2151A, and 2151E photo-
electronic detector heads. The capability of plugging these
detectors into a variety of special bases makes them more
versatile than equivalent direct-wired models. Refer to the
System Sensor catalog for other available plug-in detector
bases.