System Sensor B200SR User Manual

Page 2

Advertising
background image

SS-450-001

2 I56-3392-007R

B200Sr TerminaLS
No. Function
1. Not Used
2. Positive (+) Comm. Line In and Out
3. Negative (-) Comm. Line In and Out
4. External Supply Positive (+)
5. External Supply Negative (-)
6. Sounder Base Interconnect

mOUnTing
Mount the B200SR mounting plate directly to an electrical box. The plate will
mount directly to 4˝ square (with and without plaster ring), 4˝ octagon, 3

1

/

2

˝

octagon, single gang or double gang junction boxes.

1. Connect field wiring to terminals, as shown in Figure 1 and 2.
2. Attach the mounting plate to the junction box as shown in Figure 3.
3. To mount the sounder base, hook the tab on the sounder base to the groove

on the mounting plate.

4. Then, swing the sounder base into position to engage the pins on the

product with the terminals on the mounting plate.

5. Secure the sounder base by tightening the mounting screws.
6. Install a compatible smoke sensor as described in the installation manual

for the sensor.

TeSTing and mainTenanCe
Sensors and bases must be tested after installation and as an integral part of a
periodic maintenance program. Test the B200SR as follows:

NOTE: Before testing, notify the proper authorities that the smoke sensor
system is undergoing maintenance and, therefore, will be temporarily out of
service. Disable the system undergoing maintenance to prevent unwanted
alarms.
1. If configured as in Figure 4 and 5, reverse the polarity of the external 24VDC

supply. If configured as in Figure 5, turn on the Intelligent Relay Module.
All B200SR bases on the loop should sound.

2. Latch the sensor LED on from the control panel. That individual sensor’s

B200SR should sound.

When performing maintenance on connected smoke sensors, carefully note
the location and address of each removed sensor.

figUre 3: mOUnTing

figUre 2:

Location of jumper–

remove to enable

continuous tone

C0471-07

C0473-00

C0891-08

figUre 1:

1

2

3

4

5

6