WIRINg INSTRUCTIONS
Make wiring connections by stripping about

3

8

of an inch (10 mm) of insula-

tion from the wire end. Then, insert the wire into the appropriate terminal and
tighten the screw. Wire the communication line in (+) to terminal 1. Insert
both communication line in (–) and communication line out (–) to terminal 2.
Wire communication line out (+) to terminal 3 (see Figures 3 and 4).

A label is affixed to the base for recording the zone, address, and type of
detector being installed at the base location. This information is useful for set-
ting the detector head address and for verification of the sensor type required
for that location.

Once all detector bases have been wired and mounted, and the loop wiring
has been checked, the detector heads may be installed in the bases.

fIgURE 5A. ACTIvATINg ThE TAMPER-RESIST fEATURE:

PLASTIC LEVER

BREAK TAB AT DOTTED LINE BY

TWISTING TOWARD CENTER OF BASE.

USE SMALL-BLADED SCREWDRIVER TO PUSH

PLASTIC LEVER IN DIRECTION OF ARROW.

C1065-00

Please refer to insert for the Limitations of Fire Alarm Systems

SS-450-002

2 I56-3736-001R

©2011 System Sensor

ThREE-YEAR LIMITED WARRANTY

System Sensor warrants its enclosed smoke detector base to be free from defects in ma-
terials and workmanship under normal use and service for a period of three years from
date of manufacture. System Sensor makes no other express warranty for this smoke
detector base. No agent, representative, dealer, or employee of the Company has the au-
thority to increase or alter the obligations or limitations of this Warranty. The Company’s
obligation of this Warranty shall be limited to the replacement of any part of the smoke
detector base which is found to be defective in materials or workmanship under normal
use and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System Sensor, Returns

Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include
a note describing the malfunction and suspected cause of failure. The Company shall
not be obligated to replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date of manufacture.
In no case shall the Company be liable for any consequential or incidental damages for
breach of this or any other Warranty, expressed or implied whatsoever, even if the loss
or damage is caused by the Company’s negligence or fault. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation
or exclusion may not apply to you. This Warranty gives you specific legal rights, and you
may also have other rights which vary from state to state.

SLOT

SLOT

C1082-00

TAMPER-RESIST fEATURE
NOTE: Do not use the tamper-resist feature if the removal tool is to be used.

This detector base includes a tamper-resist feature that prevents its removal
from the base without the use of a tool.

To activate this feature, break the tab from the detector base as shown in Fig-
ure 5A. Then, install the detector.

To remove the detector from the base once the tamper-resist feature has been
activated, insert a small-bladed screwdriver into the slot from the top and
press down on the lever (see Figure 5B). This allows the detector to be rotated
counterclockwise for removal.

The tamper-resist feature can be defeated by breaking and removing the plastic
lever from the base. However, this prevents the feature from being used again.

(+)

(–)

(–)
(+)

(–)
(+)

(+)

(–)

(–)
(+)

(–)
(+)

3 (+)

2 (–)

2 (–)

1 (+)

2 (–)

1 (+)

3 (+)
2 (–)

(+)

(–)

(–)
(+)

(+)

(–)

(–)
(+)

2 (–)

2 (–)

3 (+)

1 (+)

2 (–)

2 (–)

3 (+)

1 (+)

(+)

(–)

COMMUNICATION LINE

ALL WIRING SHOWN IS SUPERVISED.

A PAIR OF FAULT ISOLATOR BASES WILL

DISCONNECT A GROUP OF DEVICES IF A

SHORT CIRCUIT OCCURS ON THE SIGNALING

LINE CIRCUIT WITHIN THAT GROUP.

GROUPS OF ADDRESSABLE DEVICES ARE

SEPERATED BY FAULT ISOLATOR BASES. ANY

COMBINATION OF COMPATIBLE LISTED DEVICES

MAY BE MIXED WITHIN A GROUP

COMPATIBLE

CONTROL PANEL

GROUP 1

GROUP 2

GROUP 3

C1013-01

fIgURE 4. WIRINg DIAgRAM:

fIgURE 5B. REMOvINg ThE DETECTOR hEAD fROM ThE BASE: