System Sensor B401 User Manual

B401 plug-in detector base

Advertising
background image

D450-08-00

1

I56-338-09R

B401 Plug-In Detector Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing
Please thoroughly read System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which pro-
vides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available from System Sensor.

NOTICE: This manual should be left with the owner/user
of this equipment.

IMPORTANT: The detector used with this base must be
tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.

Specifications
Base Diameter:

10.2 cm (4.0 inches)

Base Height:

2.0 cm (0.8 inches)

Weight:

152 g (0.34 lb.)

Mounting:

50 mm box
60 mm box

Operating Temperature Range:

–10° to +60°C (14° to 140°F) — European Installation
0° to 49°C (32° to 120°F) — US/Australian Installation

Operating Humidity Range:

10% to 93% Relative Humidity

Electrical Ratings — includes base and detector

Base And Smoke Detector

Base And Heat Detector

System Voltage:

12/24 VDC

24 VDC

Maximum Ripple Voltage:

4 Volts peak to peak

4 Volts peak to peak

Start-up Capacitance:

0.02 µF Maximum

0.02 µF Maximum

Standby Ratings:*

8.5 VDC Minimum

15 VDC Minimum

35 VDC Maximum

35 VDC Maximum

120 µA Maximum

100 µA Maximum

Alarm Ratings:

4.2 VDC Minimum at 10 mA**

4.2 VDC Minimum at 10 mA**

6.6 VDC Maximum at 100 mA**

6.6 VDC Maximum at 100 mA**

Reset Voltage:

2.5 VDC Minimum

2.5 VDC Minimum

Reset Time:

0.3 Seconds Maximum

0.3 Seconds Maximum

Start-up Time:

34 Seconds Maximum

34 Seconds Maximum

* 1151E: 30 µA Maximum.
** Alarm current MUST be limited to 100 mA maximum (130 mA for models 1151 and 2151) by the control panel.

If used, the RA400Z Remote Annunciator operates within the specified detector alarm currents.

General Description
This B401 plug-in detector base is used with System Sensor
smoke and heat detector heads. The capability of plugging
these detectors into a variety of special bases makes them
more versatile than equivalent direct-wired models. Refer
to the System Sensor catalog for other available plug-in
detector bases.

The B401 base is intended for use in 2-wire systems, with
screw terminals provided for power and remote annuncia-
tor connections.

For use with the following detectors:
US Models:

1151, 1451, 2151, 2451, 2451TH, 5451

European Models:

1151E, 1451E, 2151E, 2451E, 5451E

Australian Models:

1151AUS, 1451AUS, 2151AUS, 2451AUS, 4451AUS
5451AUS, 51A51, 51B51, 51C51, 51D51