System Sensor B224RB User Manual

B224rb plug-in relay detector base

Advertising
background image

SS-450-003

1 I56-3737-002R

B224rB Plug-in
relay detector Base

inSTaLLaTiOn and mainTenanCe inSTrUCTiOnS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

BefOre inSTaLLing
Please read the System Smoke Detector Applications Guide, which provides
detailed information on detector spacing, placement, zoning, wiring, and spe-
cial applications. Copies of this application guide are available from System
Sensor. NFPA 72 guidelines should be observed.

NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with these bases must be tested and main-
tained regularly following NFPA 72 requirements. The detectors should be
cleaned at least once a year.
generaL infOrmaTiOn
The relay base is intended for use in an intelligent system. Form C latching
relay contacts are included for the control of an auxiliary function. The relay
can operate in two different modes (short and long delay). The activation time
when the short delay is used is 60 msec to 100 msec, while the activation time
for the long delay is 6 sec to 10 sec. A shunt with pin headers, located on the
base PC board, can be used to choose your desired delay. B224RB is set at
the short delay when manufactured. If you wish to use the long delay, please
move the shunt to the adjacent pair of pin headers. See Figures 2 and 6.
B224rB TerminaLS
nO. fUnCTiOn
1. Normal Close
2. Common
3. Normal Open
4. Comm. Line In (–) and Out (–)
5. Comm. Line In (+) and Out (+)

SPeCifiCaTiOnS
Base Diameter:

6.85 in (17.4 cm)

Base Height (less sensor):

1.61 in (4.1 cm)

Operating Temperature Range:

Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com

Operating Humidity Range:

10% to 93% Relative Humidity (Non-condensing)

Electrical Ratings
Operating Voltage:

15 to 32 VDC

Standby Current:

170 µA

Relay Characteristics
Coil:

2 coil latching

Contact Type:

Form C

Contact Relay Ratings

Set Time (Position 1):

60 msec minimum, 100 msec maximum

Set Time (Position 2):

6 seconds minimum, 10 seconds maximum

Reset Time:

20 msec

mOUnTing
Mount the mounting plate directly to an electrical box. The plate will mount
directly to 4-inch square (with and without plaster ring), 4-inch octagon, 3

½-inch octagon, single gang and double gang junction boxes.
1. Connect field wiring to terminals, as shown in Figure 4.
2. Attach the mounting plate to the junction box as shown in Figure 2.
3. To mount the base, hook the tab on the base to the groove on the

mounting plate.

4. Then, swing the base into position to engage the pins on the product

with the terminals on the mounting plate.

5. Secure the base by tightening the mounting screws.
6. Install a compatible smoke detector as described in the installation

manual for the detector.

I56-3737-00

2R

1

2

3

4

5

figUre 1. TerminaL deSignaTiOn:

C0471-06

CUrrenT raTing

maXimUm VOLTage

LOad deSCriPTiOn

aPPLiCaTiOn

2 A

25 VAC

General purpose (PF = 0.35)

Non-coded

3 A

30 VDC

General purpose

Non-coded

2 A

30 VDC

General purpose

Coded

0.46 A

30 VDC

(L/R = 20ms)

Non-coded

0.7 A

70.7 VAC

General purpose (PF = 0.35)

Non-coded

0.3 A

110 VDC

General purpose

Non-coded

0.9 A

125 VDC

General purpose

Non-coded

0.5 A

125 VAC

General purpose

Non-coded

0.3 A

125 VAC

General purpose (PF = 0.35)

Non-coded

0.24 A

220 VDC

General purpose

Non-coded

0.25 A

250 VAC

Resistive load

Non-coded