System Sensor B501BHT-2 User Manual

Page 3

Advertising
background image

D250-02-00

3

I56-2814-003R

Figure 4. Wiring diagram:
Detector Activates Sounder Base(s) - (Complies with UL268)
UL has approved grouping for up to six B501BHT-2 base with
horn units. When wired as a group, any detector in the group
that has its LED’s latched on by the panel will cause other
B501BHT-2 units in the group to sound. This type of “local”
grouping is accomplished by wiring the grouped devices to-

U.L.

LISTED

EOL

RESISTOR

47K

U.L.

LISTED

EOL

RELAY

24V

5

4

1

2

3

5

4

1

2

3

5

4

1

2

3

(+) SLC

(–) SLC

(–) POWER

(+) POWER

U.L. LISTED COM

P

A

TIBLE

CONTROL

P

ANEL

EXTERNAL 24V SUPPL

Y

CLASS A OPTIONAL WIRING

CLASS A OPTIONAL WIRING

*GROUPING OF UP TO 6 MODEL B501BHT-2 TEMPORAL TONE SOUNDER BASES.

OPTIONAL SOUNDER INTERCONNECT

*

(+) SLC

(–) SLC

SUP

(–)

SUP

(+)

INTELLIGENT

MONITOR MODULE

gether using terminal 5, Sounder Base Interconnect, as shown
in the diagram.
NOTE: Since a local grouping of horns is not supervised, the
groups can only be used as a supplementary evacuation system.
It is not acceptable to group horns for primary alarm signaling.

C0474-05

UL LISTED

COMPATIBLE

CONTROL

PANEL

INTELLIGENT

RELAY

MODULE

FIRST

SOUNDER

BASE

(+) POWER

(–) POWER

LAST

SOUNDER

BASE

(–) SLC

(+) SLC

UL

LISTED

EOL

RELAY

24V

UL LISTED

EOL

RESISTOR

47k

UL LISTED

24V SUPPLY

SLC

THIS IS A STANDARD RELAY

MODULE CONFIGURED TO

REVERSE THE POWER

OPTIONAL SOUNDER INTERCONNECT

*

(+) SLC

(–) SLC

SUP

(–)

SUP

(+)

INTELLIGENT

MONITOR MODULE

(+) SLC

NO 1

NO 2

NC 2

COMM 2

COMM 1

NC 1

(–) SLC

*

GROUPING OF UP TO 6 MODEL B501BHT-2 TEMPORAL TONE SOUNDER BASES.

Figure 5. Wiring diagram:
Detector Activates Sounder Base(s); Intelligent Relay Module Ac-
tivates All Sounder Bases - (Complies with UL 268 and UL 464)
UL has approved grouping for up to six B501BHT-2 base with
horn units. When wired as a group, any detector in the group
that has its LED’s latched on by the panel will cause other
B501BHT-2 units in the group to sound. This type of “local”

C0973-01

grouping is accomplished by wiring the grouped devices to-
gether using terminal 5, Sounder Base Interconnect, as shown
in the diagram.
NOTE: Since local grouping of horns is not supervised, the
groups can only be used as a supplementary evacuation system.
It is not acceptable to group horns for primary alarm signaling.