System Sensor EA-CT User Manual

Page 3

Advertising
background image

D800-20-00 3 I56-2245-005

% DiRTy
0000

If the device is a photo-duct detector, the following screen will appear:

PHO-DucT
DeTecTOR

If the down arrow is pressed again, a screen similar to this one will appear:

S1:xxx
S2:xxx

This screen shows the levels of sensitivity for the selected device. Pressing the
down arrow again will show how dirty the detector is. This is indicated as the
percentage of drift compensation limit used. Please refer to the control panel
installation manual for the percentage that requires cleaning.

If the device is a photo detector, the following screen will appear:

PhotoDcT
Detector

If the down arrow is pressed again, a screen similar to this one will show up if
the device is configured to Acclimate.

aHiS: 0.5
aLOS: 4.0

This screen shows the Acclimate sensitivity range of the photo detector. The
AHIS is the upper limit of the sensitivity range in percent per foot. The ALOS
indicates the lower limit of the sensitivity range in percent per foot. Detector
sensitivity cannot be changed using the EA-CT. Please refer to the control
panel installation manual to change the levels of sensitivity on the detector.

If the down arrow is pressed again a screen similar to this one will appear:

SenS
LeveL: 2.4

If the device is not configured to Acclimate the following screen similar to this
one will appear:

S1:xxx
S2:xxx

This shows the sensitivity level corresponding to the sensitivity broadcasts.
Pressing the down arrow again will show the how dirty the detector is. This
is indicated as the percentage of drift compensation limit used. Please refer to
the control panel installation manual for the percentage that requires cleaning.

If the device is an Ion detector, the following screen will appear:

iOn Se
DeTecTOR

If the down arrow is pressed again, a screen simliar to this one will show up if
the device is configured to Acclimate:

aHiS.x.x%
xxMic

If the down arrow is pressed again, a screen simliar to this one will show up:

aLOS x.x%
xxMic

If the down arrow is pressed again, a screen similar to this one will appear:

SenS x.x%
xxMic

If the device is not configured to Acclimate a screen similar to this one will appear:

S1: x.x%
xxMic

If the down arrow is pressed again, a screen similar to this one will appear:

S2: x.x%
xxMic

This shows the sensitivity level corresponding to the sensitivity broadcasts.
Pressing the down arrow again will show how dirty the detector is. This is
indicated as the percentage of drift compensation limit used. Please refer to
the control panel installation manual for the percentage that requires cleaning.

If the device is a control module, the following screen will appear:

cOnTROL
MODuLe

If the device is a relay module, the following screen will appear:

ReLay
MODuLe

If the device is a monitor module, the following screen will appear:

MOniTOR
MODuLe

If the device is mini module, the following screen will appear:

Mini
MODuLe

If the device is a pull station, the following screen will appear:

PuLL
STaTiOn

If the device is conventional zone module, the following screen will appear:

cOnv ZOn
MODuLe

If the device is dual monitor module, the following screen will appear:

DuaL MOn
MODuLe

When the down arrow is pressed again on all ECLIPSE devices the screen will
show the date when each device was last serviced (if the service data was
set during the last service). If the Menu Settings are set to US format the date
format will be MM/DD/YY. If the settings are Non-US setting the date will be
displayed as DD/MM/YY.

SeRviceD
07/16/12

When the down arrow is pressed again on all devices, the display will show the
date the device was manufactured in weeks of the year followed by the year.

Manuf.:
WK: 02,11

4. WRiTe SeRvice
This setting allows a service technician to record when the selected Eclipse de-
vice has been serviced. When this choice is made, the EA-CT will request the
user to point to the selected device, and if the communication is successful, a
screen similar to the following is displayed:

SeRviceD:
10/10/95

NOTE: The service date is automatically entered as the current date and can-
not be changed to a different day.

5. TeST MODeS

5.1 TeST aLaRM

This option will cause a device to self-test. Point to the selected device that re-
quires testing and press enter. When the communication is complete, a screen
similar to this will be displayed:

OK aLaRM TeST SeT

Optionally “

SE” will appear if smoldering is enabled

Reporting the Acclimate Hi sensitivity

Reporting the Acclimate Low sensitivity

Showing the current detector’s sensitivity

Advertising