System Sensor RR2 User Manual

Page 4

Advertising
background image

D500-44-00 4 I56-1683-02

© System Sensor 2003

System Sensor warrants its enclosed relay module to be free from defects
in materials and workmanship under normal use and service for a period
of three years from date of manufacture. System Sensor makes no other
express warranty for this smoke detector. No agent, representative, dealer,
or employee of the Company has the authority to increase or alter the
obligations or limitations of this Warranty. The Company’s obligation of
this Warranty shall be limited to the repair or replacement of any part of
the smoke detector which is found to be defective in materials or work-
manship under normal use and service during the three year period com-
mencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Department,

RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include
a note describing the malfunction and suspected cause of failure. The
Company shall not be obligated to repair or replace units which are found
to be defective because of damage, unreasonable use, modifications, or
alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach
of this or any other Warranty, expressed or implied whatsoever, even if
the loss or damage is caused by the Company’s negligence or fault. Some
states do not allow the exclusion or limitation of incidental or consequen-
tial damages, so the above limitation or exclusion may not apply to you.
This Warranty gives you specific legal rights, and you may also have other
rights which vary from state to state.

Three-Year Limited Warranty

Testing
Before testing, notify the proper authorities that the system
is undergoing maintenance and will temporarily be out of
service.

Test in accordance with NFPA 72 test methods, inspections,
and testing frequency.

1. Confirm that all smoke detectors connected to the RR2

module(s) contain a sounder and the sounders are acti-
vated upon power reversal.

2. Initiate an alarm with one of the smoke detectors con-

nected to the RR2 module using any approved test
method. In the alarm state, all the detectors connected
to the RR2 module must be sounding their sounders.

3. Reset the system from the control panel. All smoke

detector sounders should be silent.

4. If the fire alarm panel also functions in burglary mode,

initiate a burglary alarm and ensure the smoke detectors
do not sound.

S0112-00

EOL

+

+

A
A

Power

+

+

Power

NC

NO

C

Aux

A
A

NC

NO

C

Aux

DSC POWER 832

RR2

AUX (+)

PGM2

PGM1

AUX –

AUX +

ZONE (+)

ZONE (COM)

PURPLE

YELLOW

ORANGE

RED

BLACK

BROWN

WHITE

5.6

K

Ω*

*NOTE: 5.6K

Ω resistor must be rated for 1/4W or greater.

Figure 7. Connecting 2112/24AT, 2112/24ATR, and 2112/24AITR smoke detectors to DSC Power 832 con-
trols using RR2 module with PGM output:

All smoke detectors on the 4-wire fire
zone will sound temporal 3 only from a
fire alarm event.
NOTE: • Program zone section attributes

for bell output to be pulsing.

• PGM2 must be programmed for

sensor reset.

• PGM1 must be programmed as

Burglary and Fire Bell Output (01)
with ON, ON, OFF attributes.

• RR2 switch must be set to OFF

(factory default setting).

Connection diagrams with DSC Power 832 Panels