Surface Wiring Mounting Instructions
1. Read the installation instructions appropriate for the

detector head to be used and determine the number of
wires used.

2. Drill out the appropriate holes using the drill centers

provided on the sides of the adaptor (see Figure 4).
Do not use conduit larger than 1/2″ to connect to the
SMB600.

3. Mount the adaptor on the ceiling using the 2 keyholes

and appropriate screws or bolts (not included). The
screws or bolts must be long enough to go through the
adaptor (5/32″ or 4mm) and still fasten securely to the
ceiling.

4. Pull wiring and conduit through the drilled hole(s). Attach

nut(s) (not included) to conduit fitting and tighten.

DRILL

CENTERS (4)

Figure 4. Drill centers:

C0525-00

5. Wire detector base using the instructions included with

the base.

6. Mount the base, using the supplied screws, in the

SMB600 Surface Mounting Adaptor Kit.

NOTE: When using the B402, B404, or B406 with the sur-

face mount base, the 4 alignment ribs (see Figure
1) must be cut off flush or below the top edge of
the surface mount base (see Figure 2).

7. Plug the detector head into its mounting base and rotate

clockwise.

8. Test the system as indicated in the detector instruction

manual.

D650-02-00 2 I56-444-04