Magnetic Testing
To attach the magnet to the pole:
1. Pull the connecting pin and remove the Installation/

Removal head from the pole assembly.

2. Push and hold the lock button, and remove the con-

necting tube from the pole.

3. Remount the other end of the connecting tube to the

pole, making sure that the lock button snaps into place.

4. Slide the magnet into the slots and cover with the plastic

cap.

To Test The Detector:
1. Hold the test magnet near the raised mark on the smoke

detector in one of the test areas shown in Figure 3.

NOTE: If the smoke detector does not alarm after 20 sec-

onds, move the magnet to the other test area and
repeat.

2. Smoke detector LEDs should light and panel should in-

dicate alarm.

3. Push the reset button on the panel to reset the smoke

detector.

4. See the smoke detector manual for additonal infor-

mation.

WARNING

When using the XR2B removal tool with the XP-4 extension
poles, avoid any contact with overhead wiring. The wood
insulators in the extension poles are not effective in all
shock hazard situations.

Figure 2. Insertion of detector head
into cup of XR2B:

LED Status

Indicators

Magnet Test

Marker

Test Magnet

Position

Test Magnet

Position

Magnet Test

Marker

Figure 3. Test Magnet Position:

C0145-00

C0184-00

2 I56-2248-00