System Sensor 546-7000 Cover Tamper Switch User Manual

Cover tamper switch

Advertising
background image

D770-05-00

1

I56-403-03

Cover Tamper Switch

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

NOTICE: This manual should be left with the owner/user
of this equipment.

CAUTION

Do not leave unused wires exposed. Do not use in poten-
tially explosive atmospheres.

General Information
This cover tamper switch mounts to all System Sensor
WFD, WFDT, OSY2 and PIBV2 terminal block units. Cover
removal produces a switch output. The unit will reset when
the product cover is reinstalled.

Installation Guidelines
Before installing any cover tamper switch, be thoroughly
familiar with:

Specifications
Contact Ratings:

5.0A @ 125/250 VAC
2.5A @ 24 VDC

Overall Dimensions:

1

1

/

4

˝H x 2˝W x

3

/

4

˝D

Operating Temperature Range:

32

°

to 120

°

F (0

°

to 49

°

C)

Shipping Weight:

0.025 lb.

NFPA 72:

National Fire Alarm Code

NFPA 13:

Installation of Sprinkler Systems, specifically
section 3.17.

NFPA 25:

Inspection, Testing and Maintenance of Sprin-
kler Systems, specifically chapters 4 and 5.

Other applicable NFPA standards, local codes and the re-
quirements of the authority having jurisdiction.

Failure to follow these directions may result in failure of the
device to report an alarm or trouble condition. System Sen-
sor is not responsible for devices that have been improperly
installed, tested or maintained.

Mounting Instructions
1. Install switch mounting bracket onto terminal block us-

ing the 2 screws provided, shown in Figure 1.

2. Snap the switch onto the switch mounting bracket in po-

sition shown in Figure 1.

A78-1661-00

Figure 1. Assembly Diagram: