System Sensor i4 Series Modules User Manual

Series interface module cosmod2w and cosmod4w

Advertising
background image

SS-500-004 1 I56-3871-001

i

4

Series Interface Module

COSMOD2W and COSMOD4W

*For use with COSMO-2W and COSMO-4W detectors

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6583

www.systemsensor.com

SPECIfICATIONS
Electrical Specifications
Power Supply Voltage:

Resettable power; 2-Wire: Min. 8.5 Volts DC (Power limited); Max. 35 Volts DC (Power limited);

4-Wire: Min. 10 Volts DC (Power limited); Max. 35Volts DC (Power limited)

Device Power-up Time:

200 milliseconds

Max. Standby Current:

2-Wire: 62mA; 4-Wire: 52mA (Does not include current draw from attached detectors or EOL relay)

Max. Alarm Current:

2-Wire: 174mA; 4-Wire: 75mA (Does not include reverse polarity current draw from attached detectors)

Nom. Standby Current:

2-Wire: 45mA@12V, 27mA@24V; 4-Wire: 36mA@12V, 21mA@24V

(Does not include current draw from attached detectors or EOL relay)

Alarm Contact Rating:

100 mA @ 36 Volts DC, resistive, 25 ohms

Maintenance Contact Rating:

100 mA @ 36 Volts DC, resistive, 25 ohms

Max. IDC Loop Wiring Resistance:

2-Wire: 50 Ohms; 4-Wire: 300 Ohms

Trigger Inputs:

Min. On Voltage: 1.5V; Max. On Voltage=Vin

Aux Power Out:

Same Voltage as Input Power (Unregulated, limited to 250mA)

Min. Reset Time:

300 milliseconds

Initial Communication Cycle:

6 minutes

EZ Walk Test Availability:

6 minutes after power up or panel reset

Physical Specifications
Operating Temperature Range:

0 - 50° C (32 - 122° F)

Operating Humidity Range:

5 - 95% RH

Storage Temperature Range:

-20 - 70° C (-4 - 158° F)

Height:

6.04 inches

Width:

6.04 inches

Depth:

1.16 inches

Shipping Weight:

0.6 lbs

Wire Gauge Acceptance:

Min: 22 AWG; Max: 14 AWG

2-wire Compatibility Requirements
Min. Loop Voltage:

12.9 Volts DC

Max. Loop Voltage:

14.5 Volts DC

Max. Loop Resistance:

50 Ohms

Max. Loop Ripple:

240 mVpp

Max. Loading Capacitance:

0.01 mF

Max. Alarm Current:

46 mA

Max. Reset Voltage:

0.30 Volts DC

Alarm Delay:

n/a

Min. Alarm Reset Time:

0.3 seconds

Max. Normal Load Current:

2.4 mA

Zone Type:

Standard

EOL Device:

3.9k Ohms (+-5%)

Loop Style:

B and D

Compatibility Zone Identifier:

A

Detector Zone Identifier:

A

Max. Detectors Per Zone:

(12) 2-wire i

4

series model #COSMO-2W and/or i

3

series model #2WTA-B detectors

I56-387

1-00

1

BEfORE INSTALLATION
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
module will be installed in an existing operational system, inform the operator
and local authority that the system will be temporarily out of service. Discon-
nect power to the control panel before installing the module.

Notice: This manual should be left with the owner/user of this equipment.
This product is intended for use in ordinary indoor locations.
GENERAL DESCRIPTION
The i

4

series module is designed to interface between compatible i

4

series

combination CO/smoke detectors (Model COSMO-2W and COSMO-4W) and
compatible security/fire panels. It can also be used to retrofit compatible i

4

series detectors into an existing loop of i

3

smoke detector models 2WTA-B or

4WTA-B, without adding wires. The module interprets signals and translates
them into a separate smoke zone and a separate CO zone, each with alarm
and trouble signals. When signaled by the panel, a module will synchronize
connected detector sounders in either Temporal 3 or Temporal 4 pattern. Local
status indication is provided by 4 LED’s and a 3 position DIP switch enables
user configuration.

The i

4

COSMOD2W, 2-wire interface module, offers additional functionality

including:

• Ability to query for a “need for maintenance” condition from 2-wire i

4

series model COSMO-2W and i

3

series model 2WTA-B smoke detectors

• One relay is available to indicate a multitude of maintenance conditions

at the control panel

• All conditions are displayed at the module and at the detector

• EZ Walk test mode allows the installer to easily verify that all detectors

on a loop are operational

• Allows 2-wire smoke detectors to be used on any compatible 4-wire

control panel and provides Style D wiring on the detector loop

fEATURES

• Compatible with System Sensor i

4

series combination CO/smoke detectors

and System Sensor i

3

Series smoke detectors models 2WTA-B or 4WTA-B.

• Allows up to 12 compatible devices including the i

4

series combination

CO/smoke detector to be integrated with a panel

Advertising