D770-25-00

2

I56-1427-001R

Locate it where vibration, shock, and mechanical loading
are minimal. Refer to piping diagram (Figure 2 on page 2).

a. Mount the device directly to the line via the 1/2" NPT

pressure connection. The use of teflon pipe sealant
tape is recommended. Be sure the fitting is tight
enough to prevent leaks.

b. Apply tightening torque to the brass hex portion of

device.

High voltage. Electrocution hazard. Do not handle live AC
wiring or work on a device to which AC power is applied.
Doing so may result in severe injury or death.

3. Wire the device in accordance with the National

Electrical Code. Two 1/2” NPT conduit entry holes have
been provided in the mounting base to accept explosion
proof conduit fittings. If necessary, remove conduit entry
plug with 3/8” square wrench.

4. Connect wiring to terminals (see Figure 3 and Table 1).

Adjustments To Factory Settings

CAUTION

WET
SYSTEM
ALARM
CHECK
VALVE

OS & Y
VALVE

WATER

BY-PASS

VALVE

LOCAL ALARM

SHUT OFF

VALVE

RETARD

WATER
MOTOR
GONG

EPS10EXP

WET
SYSTEM
ALARM
CHECK
VALVE

OS & Y
VALVE

WATER

BY-PASS

VALVE

LOCAL ALARM

SHUT OFF

VALVE

RETARD

WATER
MOTOR
GONG

EPS10EXP

DRY
SYSTEM
ALARM
CHECK
VALVE

OS & Y
VALVE

WATER

BY-PASS

VALVE

LOCAL ALARM

SHUT OFF

VALVE

WATER
MOTOR
GONG

CHECK
VALVE

EPS10EXP

WET SYSTEM

WET SYSTEM

DRY SYSTEM

WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL

WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL

WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL

TO
SPRINKLER
SYSTEM

TO
SPRINKLER
SYSTEM

TO
SPRINKLER
SYSTEM

Figure 2. Typical piping diagram for EPS10EXP

A78-2398-00

Figure 3. Switch terminals:

Table 1. Electrical connections (referenced at facto-

ry settings):

COMMON
TERMINALS

TERMINAL
“A”

SWITCH #2

TERMINAL
“B”

GROUND
SCREW
(GREEN)

SWITCH #1

A78-2346-02

BREAK WIRE AS SHOWN FOR
SUPERVISION OF CONNECTION.
DO NOT ALLOW STRIPPED WIRE
LEADS TO EXTEND BEYOND
SWITCH HOUSING. DO NOT
LOOP WIRES.

SWITCHES AT 4-8 P.S.I. (HIGH TRIP PT.)

SWITCHES AT 0 P.S.I.

SW1

SW2

MODEL EPS10EXP

SW1

SW2

B

COM

A

B

COM

A

A

COM

B

A

COM

B

BOTH SWITCHES ACTIVATE SIMULTANEOUSLY