Installation
1. Back out cover tamper set screw and remove cover (Fig. 1).
2. Mounting the Switch

The device is designed to be mounted in the upright posi-
tion; side mounting is also acceptable. Locate it where
vibration, shock, and mechanical loading are minimal.
Refer to piping diagram above (Figures 2 and 3).
a. Mount the device directly to the line via the 1/2″ NPT

pressure connection. The use of teflon pipe sealant
tape is recommended. Be sure the fitting is tight
enough to prevent leaks.

A78-2397-00

Figure 3. Typical piping diagram for EPS120EXP

DRY
PIPE
VALVE

OS & Y
VALVE

WATER

BY-PASS

TEST

VALVE

LOCAL ALARM

SHUT OFF

VALVE

WATER
MOTOR
GONG

CHECK
VALVE

EPS40EXP

CHECK
VALVE

AIR LINE
SHUT-OFF
VALVE

INSTALL
BLEEDER
VALVE FOR
TESTING

EPS10EXP

DRY SYSTEM

WIRE TO SUPERVISORY
CIRCUIT OF FIRE ALARM
CONTROL PANEL

WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL

TO
SPRINKLER
SYSTEM

Table 1. Electrical connections (referenced at

factory settings):

b. Apply tightening torque to the brass hex portion of

the device.

High voltage. Electrocution hazard. Do not handle live AC
wiring or work on a device to which AC power is applied.
Doing so may result in severe injury or death.

3. Wire the device in accordance with the National

Electrical Code. Two 1/2″ NPT conduit entry holes have
been provided in the mounting base to accept explosion
proof conduit fittings. If necessary, remove conduit entry
plug with 3/8” square wrench.

4. Connect wiring to terminals (see Figure 4 and Table 1).

CAUTION

WET
SYSTEM
ALARM
CHECK
VALVE

OS & Y

VALVE

OS & Y

VALVE

WATER

BY-PASS

VALVE

AIR

PRESSURE

SUPPLY

BLEEDER

TEST

VALVE

EPS120EXP

LOCAL ALARM

SHUT OFF

VALVE

RETARD

WATER
MOTOR
GONG

A78-2398-02

COMMON

TERMINAL

SWITCH #2
(LOW SWITCH)

TERMINAL
“B”

GROUND
SCREW

Figure 4. Switch location:

WARNING

To prevent ignition of hazardous atmospheres, disconnect
circuits before removing cover. Keep cover closed while cir-
cuits are live. Conduit runs must have sealing fittings con-
nected within 18” of the enclosure.

SWITCH #1

(HIGH SWITCH)

Figure 2. Typical piping diagram for EPS40EXP

SW2

SW1

SWITCHES AT NORMAL SYSTEM PRESSURE

SWITCHES AT LOW TRIP POINT

SW1

SW2

MODELS EPS40EXP, EPS120EXP

SWITCHES AT HIGH TRIP POINT

SW1

SW2

B

COM

A

B

COM

A

B

COM

A

A

COM

B

A

COM

B

A

COM

B