Advertising
background image

3. Mount bell mechanism on 4

square electrical box with the striker facing down. See Figures 2 – 5.

4. Replace the gong.

5. The top of the bell must be mounted a minimum of 90

above the floor, or within 6

of the ceiling.

A78-2390-00

Wire KBS 120 VAC powered bells per control panel manufacturer’s instructions.

Figure 1. Typical KMS Bell Wiring Diagram (shown in alarm condition)

BASIC MECHANISM AND GONGS

SURFACE INSTALLATION

A78-1562-01

A78-2387-00

Figure 2.

Figure 3.

WEATHERPROOF INSTALLATION

CONCEALED CONDUIT INSTALLATION

(SEMI-FLUSH)

A78-2388-00

A78-2389-00

Figure 4.

Figure 5.

10" BELL

ELECTRICAL BOX
(NOT INCLUDED)

ADAPTOR PLATE
(NOT INCLUDED)
PART NO. P40-86-03

4" SQUARE
WEATHERPROOF BACK
BOX (NOT INCLUDED)
MODEL NO. WBBF

8" BELL

8" BELL

4" SQUARE
ELECTRICAL BOX
(NOT INCLUDED)

3-1/8"

3-3/8" SQUARE

MOUNTING HOLE PATTERN

(HOLES ARE LOCATED TO MOUNT TO A

STANDARD 4" SQUARE OUTLET BOX)

10"

8"

6"

STRIKER LOCATED ON BOTTOM
OF BELL (VISIBLE FROM REAR)

3-3/8"

KMS BELL

KMS BELL

24 VDC
INDICATING
CIRCUIT FROM
FIRE ALARM
CONTROL
PANEL

EOL RESISTOR
(SPECIFIED
BY PANEL
MANUFACTURER)

DO NOT LOOP WIRE UNDER TERMINALS; BREAK WIRE RUN TO PROVIDE SUPERVISION
OF CONNECTIONS.

POLARITIES ARE SHOWN IN ALARM.

D770-06-00