System Sensor LFD Models User Manual

Page 3

Advertising
background image

Break wire as shown for
supervision of connection.
DO NOT allow stripped wire
leads to extend beyond
switch housing. Do NOT
loop wires.

D770-30-00

3

I56-1620-002R

Figure 3. Wiring LFD to bell:

BELL

BELL

POWER SOURCE

A B

C

OM

POWER
TERMINALS

AUX RELAY
TERMINALS

Figure 7. Wiring the LFD to a panel and other device:
Leave the Relay Wires installed under the Power Terminals and connect
the panel initiating loop wires as shown below. The LFD requires power
to operate, therefore connect the FACP initiating loop wires to the Power
Terminals and Relay Wires as shown. If power should be interrupted
before the panel, the batteries in the panel will maintain power to the
LFD.

EOL

OR NEXT
DEVICE

FACP

POWER SOURCE

BELL

BELL

A B COM

POWER
TERMINALS

AUX RELAY
TERMINALS

RELAY
WIRES

Figure 6. Wiring the LFD to a panel:
Leave the Relay wires installed under the Power Terminals and connect
the panel initiating loop wires as shown below.

OR NEXT
DEVICE

POWER
TERMINALS

AUX RELAY
TERMINALS

A B

C

OM

EOL

FACP

RELAY
WIRES

TO NEXT MODULE
OR EOL

INTELLIGENT

MODULE

FACP

A B COM

POWER
TERMINALS

AUX RELAY
TERMINALS

RELAY
WIRES

Figure 8. (2 Wire Addressable) Wiring the LFD to an addressable

panel using the SLC loop wires for power:
Remove the Relay Wires from under the Power Terminals. Connect these
wires to the Addressable Module.

NOTE:

Consult FACP Manufacturers’ Compatibility Guide prior to
installation.

Figure 4. (4 Wire Addressable) Wiring the LFD to an addressable

panel using an auxiliary power supply for power:
Remove the Relay Wires from under the Power Terminals. Connect these
wires to the Addressable Module.

Figure 5. Wiring the LFD using 4 wires. (Aux. Power from Panel):
Remove the Relay Wires from the Power Terminals. Cut off the spade lugs
from the ends of the Relay Wires. Put wire nuts over ends of Relay Wires
as shown. Use Aux. Relay Terminals to make connection to panel and next
device as shown.

AUX. POWER
OUTPUT

INITIATING
LOOP

A B COM

POWER
TERMINALS

AUX RELAY
TERMINALS

RELAY
WIRES

FACP

EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V

EOL

NOTE:

To comply with NFPA code, never put more than two wires in
a wire nut.

Relay wires and power terminal wiring must be contained within either a
common enclosure or enclosures within 20 feet of each other with wiring
inside conduit.

CAUTION

AUX.
POWER
OUTPUT

MODULE

SLC
LOOP

A B COM

POWER
TERMINALS

AUX RELAY
TERMINALS

RELAY
WIRES

FACP

MODULE

A B COM

POWER
TERMINALS

AUX RELAY
TERMINALS

RELAY
WIRES

NOTE: PLACE MODULE EOL
RESISTOR ACROSS RELAY
WIRES INSIDE AFD COVER.

NOTE: PLACE MODULE EOL
RESISTOR ACROSS RELAY
WIRES INSIDE AFD COVER.

AFD
ENCLOSURE

AFD
ENCLOSURE

EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V