7. Slide the actuating arm into the valve until it bottoms

on the flag, but do not tighten the lever screw.

8. Open the valve to the full open position and tighten the

lever screw to hold actuating arm in position. (Actuat-
ing arm length will adjust slightly as valve is opened.)
Check to ensure that in the full open position the actu-
ating arm is not resting on the nipple.

9. Carefully close valve and note the number of handle

revolutions until the switch trips. The switch must trip
within

1⁄5

of the total travel range of the valve.

10. Wire the switch as shown in Fig. 3.
NOTE: When removing the cover of the PIBVEXP use

provided allen wrench in box.

Figure 2:

Figure 3:

SUP. SWITCH

SUP. SWITCH

TO NON-SILENCEABLE

INITIATING ZONE OF

LISTED FACP

END OF LINE

RESISTOR

TYPICAL FACP CONNECTION

TO POWER SOURCE

COMPATIBLE WITH BELL

TYPICAL LOCAL BELL CONNECTION

LOCAL

BELL

BREAK WIRE AS SHOWN FOR SUPERVISION

OF CONNECTION. DO NOT ALLOW STRIPPED

WIRE LEADS TO EXTEND BEYOND SWITCH

HOUSING. DO NOT LOOP WIRES.