System Sensor PSP1 User Manual

Psp1 plug-in special purpose supervisory switch

Advertising
background image

D770-15-00 1 I56-0984-005R

PSP1 Plug-in Special Purpose
Supervisory Switch

U. S. Patent Number: 6,037,867

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Specifications
Dimensions: 4.73″ L x 2.94″ W x 2.21″ D (12 cm L x 7.5 cm W x 5.6 cm D)
With bracket – 8.5″ L (21.5 cm L)
Weight: 1.7 lbs. (.774kg)
Enclosure Rating: Cast-aluminum rain-tight outlet box, Indoor/Outdoor NEMA 3
Tamper Protection: Cover tamper switch and tamper-proof cover screws
Operating Voltage: 6/12/24 volts AC/DC
Maximum Operating Current: 250 mA
Operating Temperature: –4˚ F to 149˚ F (–20˚ C to 65˚ C)

Important
Please Read Carefully and Save
This instruction manual contains important information
about the installation and operation of this supervisory
switch. This manual should be left with the owner/user of
this equipment.

General Information
The unit is intended for supervision of non-rising stem
gate valves and other valves that cannot be monitored
by conventional supervisory switches. Turning the valve
wheel will pull the plug out of the jack and close a set of
normally open contacts. A lockout will prevent reinsertion
and require removal of the cover. Tamperproof screws are
provided for the cover. Removal of cover, or cutting of cord
or ground faults will cause an open circuit. The device
should be wired to the trouble circuit of a fire alarm con-
trol panel.

Installation
1. Choose a location near the valve (safe from flooding)

and mount the bracket to the wall.

2. Rotate the box on the bracket until the plug faces the

valve. The plug must also point downward. Tighten the
locknut on the pivot.

3. Turn the valve to the full-open position. Insert the plug

into the jack. Tightly loop the 8-ft. waterproof cable
through the valve wheel and back into the box through
the cable clamp. Close valve to check that plug pulls out
and then turn valve back to full-open position. Cut the
cord to the minimum length required to make the con-
nections within the box.

4. For all exterior applications, use 1/2″ NPT, listed liquid-

tight conduit connectors.

5. Wire the device as per the circuit diagrams shown (see

Figures 2-5). Trim the unused black wire flush with the
cable casing and cap the red wire of the cover tamper
switch.

6. If a longer cable is required, use SJOW A 18-2, two con-

ductor 18-gauge stranded rubber-jacketed cable.

7. Using the adhesive pad and wire tie provided, dress the

wires away from the lock-out mechanism.

8. When installing the cover, make sure the O-rings are in

place on the cover screws beneath the cover.

Figure 1. PSP1:

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com