System Sensor WBB User Manual

Wbb weatherproof back box accessory, Installation and maintenance instructions

Advertising
background image

D770-41-00 1 I56-1893-005

©

2004 System Sensor

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS

WBB
Weatherproof Back Box
Accessory

Specifications
Dimensions:
Box: 4.33″L × 1.55″W × 4.33″H
Foam gasket: 0.125″ thick, adheres to box top
Conduit opening: (2)

1

2

″ NPT, fully threaded with

(2)

1

2

″ NPT plug, (1)

7

8

″ knockout plug

Rear mounting tabs with 0.25″ diameter eyelets
Top mounting holes, #8-32 × 0.50″ DP

Figure 1: SpectrAlert horn, strobe, and horn/strobe
(‘K’ suffix models) mounting with universal plate

WBB

Gasket

Plate

Flat Head
Screw (4 total)

Paper Liner
For Plate
Gasket

Conduit
Entrance

Slot

Locking Rib

A0135-01

1. Mount back box in desired location (See Figure 1).
2. Install

1

2

″ NPT plug into unused conduit opening.

3. For SpectrAlert models, mount plate to back box using 4

#8-32 x

1

2

″ screws (Figure 1)supplied with product.

4. Complete field wiring.
5. Remove paper liner on plate gasket – NOTE: Perform elec-

trical tests first, then remove liner. Paper liner must be
removed from gasket before final installation.

6. Insert locking rib into slot on plate.
7. Press into plate; the SpectrAlert model will make a

“click” when it has locked into place.

NOTE: The weatherproof or outdoor notification appli-

ance must be used with the System Sensor
WBB back box when installed in applications
requiring the appliance to be weatherproof or
outdoor-listed. In such applications, using a back
box other than the System Sensor WBB will void
the UL designation.

NOTE: All System Sensor weatherproof wall-mount

horns and horn/strobes can be surface mounted
or flush mounted when used with the System
Sensor
WBB.

This accessory is UL listed for use with:
• H12/24K, S1224MCK, P1224MCK, and P12015K series

SpectrAlert® wall horn, strobe and horn/strobe models

• SSM24 and SSV120 series alarm bells

Refer to specific model installation instructions for weath-
erproof rating, temperature operating range, indoor and
outdoor application information.

Figure 2: Typical SSM and SSV bell weatherproof
installation

PAN HEAD SCREW

(4 TOTAL)

CONDUIT
ENTRANCE

GASKET

WBB

W0169-01

1. Mount back box in desired location (See Figure 2).
2. Install

1

2

″ NPT plug into unused conduit opening.

3. For SSM24 and SSV120 alarm bells, remove gong (refer

to SSM and SSV bell series installation manual) and
complete field wiring.

4. Mount bell to WBB with 4 #8-32 x

3

4

″ screws (Figure 2)

supplied with product.

Figure 3: Knockout plug removal
1. If a rear conduit entry

is required, remove the
knockout plug using a
flat blade screwdriver as
shown in Figure 3. Strike
sharply with a hammer
to pierce the wall of the
knockout plug. Move to
an adjacent wall section
and repeat until the plug falls out. Make sure that the
back box is supported adequately during this operation
to avoid injury.

2. To meet weatherproof or outdoor listing, the conduit

entrance must be gasketed.

3. Install

1

2

″ NPT plugs (2) into unused conduit openings.

Mounting Instructions

A0134-00