System Sensor SSM and SSV Models User Manual

Ssm and ssv bell series

Advertising
background image

D770-11-00 1 I56-0674-008R

SSM and SSV BELL Series

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Important
Please Read Carefully and Save
This instruction manual contains important information
about the installation and operation of bells. Purchasers
who install bells for use by others must leave this manual
or a copy of it with the user.

System Sensor supplies bells for nearly all sprinkler/fire
alarm/burglar applications.

These instructions apply to all System Sensor bells in the
series. Read all instructions carefully before beginning.
Follow only those instructions that apply to the model you
are installing.

Specifications
SSM Series:
Voltage: Regulated 24 VDC
Operating Voltage Limit: 16 - 33 VDC
Maximum Current: DC - 31.1mA/FWR - 53.5mA
Operating Temperature: –31° to 150°F (–35° to +66°C)
SSV Series:
Voltage: Regulated 120 VAC
Operating Voltage Limit: 96 - 132 VAC
Maximum Current: 53mA
Operating Temperature: –31° to 150°F (–35° to +66°C)

UL Reverberant Room

Sound Output per UL 464 (dBA)
24 VDC SSM

SSM24-6 (6″, 24 VDC, P, S) 82
SSM24-8 (8″, 24 VDC, P, S) 80
SSM24-10 (10″, 24 VDC, P, S) 81
120 VAC SSV
SSV120-6 (6″, 120 VAC) 85
SSV120-8 (8″, 120 VAC) 82
SSV120-10 (10″, 120 VAC) 82
P = Polarized
S = Suppressed

NOTE: All SSM Series DC bells were only tested at the
16–33 Volt-DC/FWR limits. All SSV Series AC bells were
only tested at the 96–132 Volt AC limits. This does not
include the 80% low-end or 110% high-end voltage limits.

General Description
The National Fire Protection Association has published
codes, standards, and recommended practices for the
installation and use of the above appliances. It is recom-
mended that the installer be familiar with these require-
ments, with local codes, and any special requirements of
the authority having jurisdiction.

These bells are intended to be connected to alarm indicat-
ing circuits of UL listed fire alarm control panels. The SSM
series is polarized to enable supervision of the installation
wiring. The SSM bells require 24 VDC and the SSV bells
require 120 VAC.

CAUTION

Do not use in potentially explosive atmospheres.

Do not leave any unused wires exposed.