System Sensor WFD Models User Manual

Page 3

Advertising
background image

D770-01-00

3 I56-0459-018R

WARNING

High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a
device to which AC power is applied. Doing so may result in injury or death.

When utilizing switches at voltages greater than 74VDC

or 49VAC

means to provide all–pole disconnection must be incorporated in the fixed
wiring, such as a circuit breaker.

fiGUre 4. WfD WirinG:

+

+

SSM24-X

SSV120-X

NOTE: COMMON AND B-NO

CONNECTIONS WILL CLOSE

WHEN VANE IS DEFLECTED, I.E.,

WHEN WATER IS FLOWING. DUAL

SWITCHES PERMIT

APPLICATIONS TO BE COMBINED

ON A SINGLE DETECTOR.

BREAK WIRE AS

SHOWN FOR

SUPERVISION OF

CONNECTION. DO

NOT ALLOW

STRIPPED WIRE

LEADS TO EXTEND

BEYOND SWITCH

HOUSING. DO NOT

LOOP WIRES.

POWER

24VDC OR

120VAC

INITIATING

LOOP

UL-LISTED

COMPATIBLE

CONTROL PANEL

CONTACT RATINGS

125/250 VAC

24 VDC

10 AMPS

2.5 AMPS

SCHEMATIC OF

INDIVIDUAL

SWITCH IN

“NO WATERFLOW”

CONDITION

SUGGESTED EOL

RESISTOR

B-NO

COM

A-NC

W0356-01

mechanicaL DeLaY aDjUsTmenT
The pneumatic delay is preset at the factory to 30 seconds. To adjust the set-
ting, turn the adjustment dial clockwise to increase the delay, counterclock-
wise to decrease it. The delay is adjustable from 0 to 90 seconds. See Figure
6, page 4.
NOTE: Set the delay to the minimum required to prevent false alarms from
flow surges.

Periodically test time delay as required by Authority Having Jurisdiction or
code authority.
operaTionaL TesTinG
Always notify a central station monitoring waterflow alarms before repairing,
maintaining, or testing waterflow alarm devices.

1. Replace the cover and tighten the tamper proof screws with the tamper

proof wrench. Store the wrench in a secure place.

2. Open the inspector’s test valve and time how long it takes for the detec-

tor to indicate a flow condition. The detector should remain activated un-
til the inspector’s test valve is closed. Air pockets in the sprinkler system
may increase the apparent delay.

mainTenance
To prevent accidental water damage, control valves should be shut tight and
the system completely drained before waterflow detectors are removed or re-
placed.

Inspect detectors in accordance with applicable NFPA codes and standards
and/or the authority having jurisdiction for leaks and replace if a leak occurs.
Test detectors at least quarterly, as described under Operational Testing, to
ensure proper operation. Test more often if required by the authority having
jurisdiction.

Under normal conditions, System Sensor waterflow detectors should provide
years of trouble-free service. However, if the delay mechanism or switch en-
closure needs to be replaced, follow these directions. To replace the delay
mechanism or switch enclosure, use a

3

/

16

˝ socket head screwdriver to remove

the three screws that hold it in place. Either mechanism can be easily replaced
without removing the detector from the pipe or draining the pipe. To replace
the delay mechanism, request Part No. A3008-00. For switch enclosure, re-
quest Part No. A77-01-02. Do not repair or replace any other waterflow detec-
tor components. If any other part of the detector does not perform properly,
replace the entire detector. Installation methods other than those listed in this
installation manual may prevent the device from reporting the flow of water in
the event the associated sprinkler system is activated by a fire. System Sensor
is not responsible for devices that have been improperly installed, tested, or
maintained.

To remove a detector:

1. Drain the pipe.
2. Turn off electrical power to the detector and disconnect the wiring.
3. Loosen the nuts and remove the U-bolts.
4. Gently lift the saddle far enough to get your fingers under it. Then, roll

the vane so it will fit through the hole while continuing to lift the water-
flow detector saddle.

5. Lift the detector clear of the pipe.

CAUTION

If a vane breaks in a pipe, find and remove it. If it is not removed, the vane
may restrict the flow of water to all or part of the sprinkler system.

fiGUre 5a. GroUnD screW LocaTion:

GROUND

SCREW

(GREEN)

MOUNTING

PLATE

W103-00

fiGUre 5b. KnocKoUT pLUG removaL:

W0148-01

fiGUre 6. DeLaY aDjUsTmenT DiaL:

DELAY

ADJUSTMENT

DIAL

55

70

0

15

45

30

TI

ME

DE

LAY IN SECO

ND

S

NU

MB

ER

ON

DIAL IS APPRO

XIM

AT

E

NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST

AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS.

NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN

SECONDS WITH AN ACCURACY OF +/− 50%.

W0112-02