System Sensor WFDT and WFDTH User Manual

Page 3

Advertising
background image

N770-05-00

3

I56-0480-013R

figUre 3. fieLD Wiring:

+

+

SSM24-X

SSV120-X

NOTE: COMMON AND B-NO

CONNECTIONS WILL CLOSE

WHEN VANE IS DEFLECTED, I.E.,

WHEN WATER IS FLOWING. DUAL

SWITCHES PERMIT

APPLICATIONS TO BE COMBINED

ON A SINGLE DETECTOR.

BREAK WIRE AS

SHOWN FOR

SUPERVISION OF

CONNECTION. DO

NOT ALLOW

STRIPPED WIRE

LEADS TO EXTEND

BEYOND SWITCH

HOUSING. DO NOT

LOOP WIRES.

POWER

24VDC OR

120VDC

INITIATING

LOOP

UL LISTED

COMPATIBLE

CONTROL PANEL

CONTACT RATINGS

125/250 VAC

24 VDC

10 AMPS

2.5 AMPS

SCHEMATIC OF

INDIVIDUAL

SWITCH IN

“NO WATERFLOW”

CONDITION

SUGGESTED EOL

RESISTOR

B-NO

COM

A-NC

W0356-00

mechanicaL DeLaY aDjUsTmenT
The pneumatic delay is preset at 30 seconds at the factory. To adjust the delay,
turn the adjustment dial on the delay mechanism. Turn clockwise to increase
the delay, counterclockwise to decrease the delay. Delay can be adjusted over
a range from 0-90 seconds. See Figure 4.
NOTE: Set the delay to the minimum required to prevent false alarms due to
flow surges.

After extended service, parts of the detector may become worn reducing the
delay time and causing false alarms. If this happens, increase the delay. If the
delay is already at maximum, replace the mechanical delay assembly. Refer to
Maintenance section for ordering replacement parts.
operaTionaL TesTing
Always notify a central station monitoring waterflow alarms before repairing,
maintaining or testing waterflow alarm devices.

1. Replace the cover and tighten the security screws with the tamper proof

wrench. Store the wrench in a secure place.

2. Open the inspector’s test valve and time how long it takes for the detec-

tor to indicate a flow condition. The detector should remain activated un-
til the inspector’s test valve is closed. Air pockets in the sprinkler system
may increase the apparent time delay.

figUre 4. DeLaY aDjUsTmenT DiaL:

DELAY

ADJUSTMENT

DIAL

55

70

0

15

45

30

TI

ME

DE

LAY IN SECO

ND

S

NU

MB

ER

ON

DIAL IS APPRO

XIM

AT

E

NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST

AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS.

NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN

SECONDS WITH AN ACCURACY OF +/− 50%.

W0112-02

mainTenance
To prevent accidental water damage, control valves should be shut tightly
and the system completely drained before waterflow detectors are removed
or replaced.

Inspect detectors in accordance with applicable NFPA codes and standards
and/or the authority having jurisdiction for leaks. Test detectors at least quar-
terly as described under Operational Testing above to insure proper operation.
This device is not designed for use on “dry pipe” systems. Test more often if
required by the authority having jurisdiction.

Under normal conditions System Sensor waterflow detectors should provide
years of trouble-free service. If, however, the delay mechanism becomes faulty,
replacement kits are available. To replace the delay mechanism, request Part
No. A3008-00; for switch enclosure, request Part No. A77-01-02. Complete
instructions are enclosed with each. Either mechanism can be easily replaced
without removing the detector from the pipe or draining the pipe. If damage
occurs to paddle, order replacement kit PRK9. Refer to procedure below for re-
moval of detector on pipe. Do not repair or replace any other waterflow detec-
tor components in the field. If any other part of the detector does not perform
properly, replace the entire detector. Failure to follow this instruction may
result in failure of the detector to report a waterflow condition.

Proceed as follows to remove a detector.

1. Drain the pipe.
2. Turn off electrical power to the detector, and then disconnect wiring.
3. Unscrew WFDT or WFDTH from tee fitting.
4. Lift detector clear of pipe.

CAUTION

If a vane breaks off in a pipe, find and remove it. Failure to do so may restrict
the proper flow of water to part of the sprinkler system.

Advertising