System Sensor ZC20 User Manual

Zonecheck flow switch tester, Installation and maintenance instructions

Advertising
background image

D770-32-00

1

I56-0053-003R

Zonecheck

Flow Switch Tester

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Important

Please Read Carefully And Save
This instruction manual contains important information about the instal-
lation and operation of a Zonecheck Flow Switch Tester. Purchasers who
install waterflow detectors for use by others must leave this manual or a
copy of it with the user.
Read all instructions carefully before beginning. Follow only those instruc-
tions that apply to the model you are installing.

Use Zonecheck Flow Switch Testers in wet-pipe systems only. Do NOT use
them in dry pipe, deluge, or preaction systems.

Do not use in potentially explosive atmospheres. Do not allow unused
wires to remain exposed.

Principles Of Operation

Retrofit Model
Zonecheck Flow Switch Tester shall mount on any clear steel pipe span of
the appropriate nominal size, either in a vertical upflow or horizontal run,
between 6″ and 12″ from the flow switch. Flow Switch Tester shall consist
of a recirculating pump, operating at nominal 110V or 220V as appropriate,
two (2) sets of valves and elbows to facilitate the circulation of the water,
a System Sensor vane-type waterflow detector, and a key switch to activate
the recirculating pump. When activated, the pump shall circulate the water
within the sprinkler riser around the waterflow detector vane to simulate
the flow of one sprinkler head in operation. The activating key switch shall
provide the means to be wired locally to one Flow Switch Tester, or inter-
connected with other key switches for group activation. Flow Switch Tester
shall be available for manifold and retrofit installation applications.

Manifold Model Specifications
Zonecheck Flow Switch Tester manifold models shall consist of a sched-
ule 10 pipe assembly of the appropriate nominal size. Manifold assembly

CAUTION

Specifications

Static Pressure Rating:

175 PSI

Operating Temperature Range: 32°F–120°F (0°C–49°C)
Compatible Pipe

(Manifold Models):

Schedule 10, 2″–4″ diameter

Compatible Pipe

(Retrofit Models):

Schedule 10 and 40, 2″–8″ diameter
(50 mm through 200 mm)

Service Use:

Inspection, Testing and
Maintenance of Water-Based
Fire Protection Systems: NFPA 25;
National Fire Alarm Code: NFPA 72

Manifold Assembly Length

(Manifold Models):

25.6″ (65 cm)

Component Connections:

Manifold Models:

Retrofit Models:

2 ea. - 1″ NPT/25mm

2 ea. - 1″ NPT/25mm British Standard

British Standard

Thread elbows

Thread elbows

2 ea. - 25mm British Standard
Thread elbows

Valves:

Red: Standard valve
Green: Contains check valve

Warranty: 3 years

shall provide grooved ends for accepting the appropriate grooved connec-
tion fittings. Manifold assembly shall include no less than two drain ports
with the appropriate drain plugs. Manifold Zonecheck models shall come
with the pump, valves, elbows, pipe assembly, drain plugs, and System
Sensor waterflow detector pre-assembled.

Manifold Models

Domestic Models with 110 V Pump

Canadian Models with 110 V Pump

ZC20, ZC25, ZC30, ZC40

ZC20A, ZC25A, ZC30A, ZC40A

Retrofit Models

Domestic Models

Canadian Models

International Models

with 110 V Pump

with 110 V Pump

with 220 V Pump

ZCR20

ZCR20A

ZCR20E

ZCR25

ZCR25A

ZCR25E

ZCR30

ZCR30A

ZCR30E

ZCR40

ZCR40A

ZCR40E

ZCR60

ZCR60A

ZCR60E

ZCR80

ZCR80A

ZCR80E

Replacement Parts

ZCK-1 Zonecheck 110V Keyswitch

ZCK-1E Zonecheck 220V Keyswitch

ZCP-110 Zonecheck 110V Pump

ZCP-220 Zonecheck 220V Pump

Do NOT install Zonecheck on copper piping.

General Installation Recommendations

Before installing any waterflow-related device, be thoroughly familiar
with: NFPA 72: National Fire Alarm Code

NFPA 13: Installation of Sprinkler Systems, Section 3.17
NFPA 25: Inspection, Testing and Maintenance of Sprinkler Systems

CAUTION

Electrical Specifications

Pump Operating Voltages:

Domestic/Canadian models:
1.63A@110 V, 60 Hz
International models: .88A@220 V, 50Hz

Key Switch Operating Voltage: ZCK-1 110V, 60Hz; ZCK-1E: 220V, 50Hz
Key Switch Mounting Options: Includes back box for surface or flush

mounting. For pre-wiring, use a
4

11

/

16

″ x 4

11

/

16

″ back box

Key Switch Operation Modes: Self-test: Wired locally

Group test: Interconnected

Key Switch LED Operation:

Ready state: No LED
Test Initiation: Green LED
Flow switch activation: Red LED

Advertising