INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEFORE INSTALLING
This information is included as a quick reference installation guide. If the
modules will be installed in an existing operational system, inform the op-
erator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably
grounded.
NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION
The CR-6 Six Relay Control Module is intended for use in an intelligent alarm
system. Each module is intended for Form-C switching applications, which do
not require wiring supervision for the load circuit. A single isolated set of dry
relay contacts is provided for each module, which is capable of being wired
for either normally open or normally closed for each operation. Each module
has its own address. A pair of rotary code switches is used to set the address
of the first module from 01 to 94. The remaining modules are automatically as-
signed to the next five higher addresses. Provisions are included for disabling
a maximum of three unused modules to release the addresses to be used else-
where. Each CR-6 module also has panel controlled green LED indicators. The
panel can cause the LEDs to blink, latch on, or latch off.

CR-6 Six Relay Control Module

SPECIFICATIONS
Normal Operating Voltage:

15-32 VDC

Stand-By Current:

1.45 mA

Alarm Current:

32 mA (assumes all six relays have been switched once and all six LEDs solid on)

Temperature Range:

32°F to 120°F (0°C to 49°C)

Humidity:

10 to 93% Non-condensing

Dimensions:

6.8˝H × 5.8˝W × 1.0˝D

Accessories:

BB-2 Cabinet; BB-6 Cabinet; CH-6 Chassis

Wire Gauge:

12-18 AWG

Relay Current:

30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

CONTENTS INCLUDE:
(6) 1 x 3 Terminal Blocks
(1) 1 x 4 Terminal Blocks
(2) 1¼˝ (32mm) Stand offs
(4) Machine Screws
(1) Shunt (NOTE: For the disable position, not more than one shunt shall be

installed at the same time)

(2) Nuts

COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
control panel only.
COMPONENTS
Following are descriptions of the CR-6 mounting frameworks. There are two
mounting options for CR-6 modules:

• Up to six CR-6 modules can be installed on a CH-6 in a BB-6 cabinet

• One or two CR-6 modules can be installed in a BB-2 cabinet

Chassis

The CH-6 chassis is used to mount CR-6 modules in a BB-6 cabinet. It accom-
modates up to six CR-6 modules in a single cabinet row three modules wide
and two modules deep.

WARNING

All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.

RELAY CONTACT RATINGS:

I56-1798-009

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

2 A

25 VAC

PF = 0.35

Non-coded

3 A

30 VDC

Resistive

Non-coded

2 A

30 VDC

Resistive

Coded

0.46 A

30 VDC

(L/R = 20ms)

Non-coded

0.7 A

70.7 VAC

PF = 0.35

Non-coded

0.9 A

125 VDC

Resistive

Non-coded

0.5 A

125 VAC

PF = 0.75

Non-coded

0.3 A

125 VAC

PF = 0.35

Non-coded