System Sensor M501M User Manual

M501m monitor module, Installation and maintenance instructions

Advertising
background image

M501M Monitor Module

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

SS-460-005

1

I56-3857-001

©2007 System Sensor

BEfORE INSTALLINg
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.
gENERAL DESCRIpTION
The M501M monitor module can be installed in a single gang junction box
directly behind the monitored unit. Its small size and light weight allow it to
be installed without rigid mounting (see Figure 1). The M501M is intended for
use in intelligent, two-wire systems where the individual address of each mod-
ule is selected using rotary decade switches. It provides a two-wire initiating
circuit for normally open contact fire alarm and security devices.
COMpATIBILITy REqUIREMENTS
To ensure proper operation, this module should only be connected to a com-
patible control panel.
fIgURE 1:

C0613-04

MOUNTINg AND WIRINg
NOTE: This module is intended to be wired and mounted without rigid con-
nections inside a standard electrical box. All wiring must conform to appli-
cable local codes, ordinances, and regulations.

1. Connect the red (+) and black (

) wires to the positive and negative

loop power leads of the signaling line circuit.

2. Connect the violet (+) and yellow (

) wires to a two-wire, normally

open initiating loop.

3. Install the specified EOL resistor value to terminate the initiating loop.
4. Set the address on the module per job drawings.
5. Install the module in the desired mounting location.
fIgURE 2. TypICAL 2-WIRE STyLE B INITIATINg
CIRCUIT CONfIgURATION:

(+)

(–)

TO

NEXT

DEVICE

BLACK

RED

(+)

(–)

(+)

(–)

VIOLET

YELLOW

0

1

2

3

4

5 6

7 8 9

SIGNAL LINE CIRCUIT (SLC)

47k EOL

INCLUDED

(ELR-47k)

UL LISTED

COMPATIBLE

CONTROL

PANEL

ALL WIRING

SHOWN IS

SUPERVISED AND

POWER LIMITED

0

7 8

6

5

4

3

2

1

9

C0614-03

SpECIfICATIONS
Nominal Operating Voltage:

15-32 VDC

Average Operating Current:

350 µA, 1 communication every 5 seconds, 47k EOL; 600 µA Max. (Communicating, IDC Shorted)

EOL Resistance:

47K Ohms

Maximum IDC Wiring Resistance:

40 Ohms

Maximum IDC Voltage:

11 Volts

Maximum IDC Current:

400µA

Temperature Range:

32°F to 120°F (0°C to 49°C)

Humidity:

10% to 93% Non-condensing

Dimensions:

1.3˝ H × 2.75˝ W × 0.65˝ D

Wire Length:

6˝ minimum

I56-3857-001