System Sensor M502M User Manual

M502m interface module

Advertising
background image

SS-460-003

1

I56-3854-001

M502M Interface Module

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Before Installing
This information is included as a quick reference installation
guide. Refer to the control panel installation manual for detailed
system information. If the modules will be installed in an existing
operational system, inform the operator and local authority that
the system will be temporarily out of service. Disconnect power to
the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of
this equipment.
General Description
The M502M Interface Module is intended for use in intelligent,
two-wire systems, where the individual address of each module
is selected using the built-in rotary decade switches. This module
allows intelligent panels to interface and monitor two-wire con-
ventional smoke detectors. It transmits the status (normal, open,
or alarm) of one full zone of conventional detectors back to the
control panel. All two-wire detectors being monitored must be UL
compatible with this module. The M502M has a panel controlled
LED indicator.
Compatibility Requirements
To ensure proper operation, these modules shall be connected to
listed compatible system control panels only.
Mounting
The M502M mounts directly to 4˝ square electrical boxes (see Figure
2A). The box must have a minimum depth of 2

1

8

˝. Surface mounted

electrical boxes (SMB500) are available from System Sensor.

Figure 1. Controls and indicators:

Figure 2A. Module mount-
ing with barrier:

Specifications

Normal Operating Voltage:

15 to 32 VDC

Maximum Current Draw:

5.1mA (LED on)

Average Operating Current:

300µA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol

EOL Resistance:

3.9K Ohms

Maximum IDC wiring resistance:

25 Ohms

IDC Supply Voltage (between Terminals T10 and T11)

Regulated DC Voltage:

24 VDC power limited

Ripple Voltage:

0.1 Volts RMS maximum

Current:

90mA per module

Temperature Range:

32˚F to 120˚F (0˚C to 49˚C)

Humidity:

10% to 93% Non-condensing

Dimensions:

4

1

2

˝ H x 4˝ W x 1

1

4

˝ D (Mounts to a 4˝ square by 2

1

8

˝ deep box.)

Accessories:

SMB500 Electrical Box

Wiring
NOTE:
All wiring must conform to applicable local codes, ordi-
nances, and regulations. This module is intended for power-lim-
ited wiring only.
1. Install module wiring in accordance with the job drawings

and appropriate wiring diagrams.

2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as

shown in Figure 2A.

Compatible Two-wire System Sensor Smoke Detectors for Use with M502M with Zone Identifier A:

Detector

Compatibility

Detector

Base

Base

Max

Model

ID

Type

Model

Identifier

Detectors

1451

A

Ionization

B401/B

A

20

2451

A

Photoelectric

B401/B

A

20

2451TH

A

Photoelectric with Thermal

B401/B

A

20

1400

A

Ionization

N/A

20

2400

A

Photoelectric

N/A

20

2400TH

A

Photoelectric with Thermal

N/A

20

1100

A

Ionization

N/A

20

1151

A

Ionization

B110LP/B401

A

20

2100

A

Photoelectric

N/A

20

2100T

A

Photoelectric with Thermal

N/A

20

2151

A

Photoelectric

B110LP/B401

A

20

*Used in combination with MTL isolator model MTL3043.

C0450-03

Figure 2B:

C0218-03

C0449-03

I56-3854-00

1