TIF 25150B Refrigerant Recovery Machine User Manual

Page 8

Advertising
background image

8

1. Allow the tank to sit undisturbed for 24 hours. This

allows the air to rise to the top.

2. Connect a manifold to the tank and read the

amount of pressure in the tank by looking at the
output pressure gauge.

3. Determine the ambient temperature in the room.

4. Refer to a Refrigerant pressure/temperature chart.

Find the temperature on the chart and look across

to the corresponding pressure for the type of

refrigerant in the tank. Determine how that relates

to the reading on the gauge.

5. If the pressure reading is higher than the pressure

shown on the chart, very slowly (so as not to
cause turbulence inside the tank) crack open the
vapor port valve. Watch the pressure on the
gauge decrease. To prevent venting, add 4-5 psi
to the pressure shown on the chart. when the
gauge corresponds to that pressure, close the
vapor port valve.

6. Allow the tank to sit for 10 minutes and check the

pressure again.

7. Repeat the process again if necessary.

PURGING NON-CONDENSABLE GASES

FROM REFRIGERANT TANK

Advertising