SELF PURGING YOUR RG5410A

PROCEDURE FOR PURGING REMAINING REFRIGERANT FROM THE RG5410A

1. Close the ports of the system being serviced that

are connected to the input port of the RG5410A.

2. Close the input port on the RG5410A.

3. Turn off the RG5410A.

4. Turn the Recover/Purge valve to the Purge posi-

tion.

5. Restart the RG5410A.

6. Run until desired vacuum is achieved.

7. Close the ports on the recovery tank and the

RG5410A.

8. Turn the RG5410A off.

9. Return the Recover/Purge valve to the Recover

position.

10.Disconnect and store all hoses.

11.Replace the in-line filter on your RG5410A

after every job.

SELF PURGE / AUTO EVACUATE

To change from Recovery mode to Purge follow the steps below:

1. Close the Input port

2. Turn the unit off (to prevent high pressure shutoff).

3. Switch to Purge position.

4. Restart the unit.

12

RECOVER

CLOSED

IN

OUT

PURGE