TREND IQ3..._..._XNC_... User Manual

TREND Accessories for electrical

Advertising
background image

1

IQ3../.../XNC/... Controller/Interface Installation Instructions TG200911 Issue 1/D 03/09/07

Important: Retain these instructions

Installation Instructions

IQ3.../.../XNC/...

Controller/Interface

CONTENTS

1

Installation - Mounting ....................................................... 1

2

Installation - Configuration ................................................ 4

3

Insertion/Replacement of battery ..................................... 7

4

Disposal ............................................................................. 8

1 Installation - Mounting

Install

1

IQ3xact Installation Instructions TG200766

IQ3xcite Installation Instructions TG200626

Install according to IQ3xact or
IQ3xcite installation instructions
section 3 steps 1 to 11

Connect Serial Interface

2

If /SER/.., serial interface auxiliary board, fitted

or RS232

4 5 6

4 5 6

2

7 8 9

7 8 9

3

10 11 12

4

13 14 15

5

16 17 18

6

19 20 21

7

22 23 24

8

25 26 27

9

28 29 30

10

+ 0

+ 0

+ 0

+ 0

+ 0

+ 0

+ 0

+ 0

+ 0

1 2 3

1 2 3

1

+ 0

+ 0

0V

24

V

24

V

34 35 36

12

37 38 39

13

40 41 42

14

A

31 32 33

P

11

43 44 45

15

46 47 48

16

100-240 V

OK RX

P 0

P 0

P 0

P 0 P 0

P 0

TX

RX

RTS/TXEN

CTS/RXEN

RS485

RS232

1

2

3

4

5

6

7

8

9

RX

TX

GND

RTS

CTS

(held high)

1

2
3

4
5
6

RX

TX

GND

RTS

CTS

either 9 way D type plug

or RJ11 socket

If RS485 2 wire

Note that only one of the two RS232 connectors can be used at a time

0V

T

A

T

B

RA

RB

0V

A B

0V

A B

0V

A B

120 ohm
terminator

Terminator switch ON

IQ3../.../SER/XNC/...

either RS485 2 wire, RS485 4 wire, or RS422

2 part connector with 5 screw terminals fo 0.5 to 2.5 mm

2

cross

section area (14 to 20 AWG) cable

If RS485 4 wire

0V

T

A

T

B

RA

RB

0V TA TB RA RB

0V TA TB RA RB

0V TA TB RA RB

120 ohm
terminators

Terminator switch ON

IQ3../.../SER/XNC/...

If RS422

0V

T

A

T

B

RA

RB

TA

TB

RA

RB

0V

Terminator switch OFF

external 100 ohm
terminator

100 ohm
terminator

IQ3../.../SER/XNC/...

32 devices maximum

32 devices maximum

Note pins 1,6,9 - no connection

Note pin 2 - no connection

Note that only one of the RS232 or RS485 connectors can have
a cable connected at any one time in order to comply with Class
B EMC emission standard (EN61000-6-3, residential, commercial,
and light industrial environments).
WARNING: Failure to comply with this requirement will reduce
the unit to Class A (industrial environments); in a domestic
environment the unit may cause radio interference, in which
case the user may be required to take adequate measures.

If the IQ3/XNC/SER controller and its slave units are in the same
cabinet using the same power supply, each device should have
a good physical earth (ground) connection.