Information sheet 963 and tops, Available bacnet properties, Data link layer options – TREND 963 and TOPS User Manual

Page 3: Device address binding, Networking options, Character sets supported

Advertising
background image

963 and TOPS BACnet PICS TP201011 Issue 2 19/01/2009

3

Information Sheet

963 and TOPS

AVAIlABle BACneT PrOPerTIeS

(Continued)

BACnet Alarms

963 can receive BACnet alarms from BACnet alarm notification classes that TOPS has subscribed to. The BACnet alarms are

converted to Trend alarms by TOPS and passed to 963. Sensor HIGH, sensor LOW, sensor READ, driver SDGT, plot BBUF, digital

input alarms are calculated using the EVENT TYPE property, and the TO Event state according to the table below. Other alarms are

assigned alarm codes by 963 see the 963 Engineering Manual for details.

BACnet Parameters

Trend Alarm

Sensor

Digital Input Driver Plot

HIgH lOW reAD DI=1

DI=0 SDgT BBuf

To Event State

normal

ü

fault

ü

offnormal

ь

ь

ь

high-limit

ü

low-limit

ü

Event Type Property CHANGE_OF_STATE

ь

ь

COMMAND_FAILURE

ü

OUT_OF_RANGE

ь

ь

ь

BUFFER_READY

ü

DATA lInk lAyer OPTIOnS:

BACnet IP, (Annex J)

BACnet IP, (Annex J), Foreign Device

ISO 8802-3, Ethernet (Clause 7)

ANSI/ATA 878.1, 2.5 MB. ARCNET (Clause 8)

ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s):

MS/TP master (Clause 9), baud rate(s):

MS/TP slave (Clause 9), baud rate(s):

Point-To-Point, EIA 232 (Clause 10), baud rate(s):

Point-To-Point, modem, (Clause 10), baud rate(s):

LonTalk, (Clause 11), medium:

Other:

DeVICe ADDreSS BInDIng:

Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other

devices.) Yes  No

neTWOrkIng OPTIOnS:

Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.

Annex H, BACnet Tunneling Router over IP

BACnet/IP Broadcast Management Device (BBMD)

Does the BBMD support registrations by Foreign Devices?

Yes  No

CHArACTer SeTS SuPPOrTeD:

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

ANSI X3.4  

IBM

/Microsoft

DBCS

ISO 8859-1

ISO 10646 (UCS-2)  

ISO 10646 (UCS-4)  

JIS C 6226

If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway

supports:

N/A