TREND PN-VPC User Manual

Pn-vpc, Electronic/pneumatic-transducer

Advertising
background image

PN-VPC

ELECTRONIC/PNEUMATIC-TRANSDUCER

PRODUCT DATA

APPLICATION

An E/P Transducer accepts a proportional voltage signal
from an electronic controller and converts it into a pro-
portional pneumatic signal of 0.2 to 1.0 bar to operate
pneumatic actuators or reset pneumatic controllers.
The PN-VPC accepts a 2...10 Vdc / 4...20 mA signal. It
includes a voltage to current converter. The PN-VPC
requires an external 24 Vac power supply.

MAINTENANCE

A full range of maintenance programs is available from your
local registered Trend office.

SPECIFICATIONS

Type No.

PN-VPC

Power supply

+10% / -15%

24 V, 50/60Hz

Power consumption

1.7 VA

Input signal

2... 10 V

Min. current at
10 Vdc

(0.1 mA)

0.02 bar (2 kPa) max. at 0 Vdc

Output pressure at
1.25 bar (125 kPa)
main pressure

1.12 bar (112 kPa) min. at 11.5 Vdc

Main air pressure

1.25 bar (125 kPa)

Main air pressure
independence

1% per 0.1 bar main air pressure

Maximum safe air

2.0 bar (200 kPa)

Air consumption

42 NL/h (700 sccm) at 0.6 bar

Air capacity

720 NL/h (12000 sccm)

Air connections

Dual-barb-fittings for either 6 x
1 mm (1/4“ O.D.) or 4 x 0.75 mm
(5/32“ O.D.) polyethylene tubing.

Calibration Factory

calibrated

Ambient temperature 5...55ºC

Storage -30...+70ºC

Humidity 5...95%

RH


All E/P-Transducers supplied with 1 m cable

WIRING

Distance
E/P-Transducer

Type of wire

length max.

to ...

100 m

150 m

Controller

local standard

1.0 mm

2

1.5 mm

2

See also Fig. 3.

NOTE: The E/P Transducer connection wire 24 V

(black) must be connected to the same potential
0 V level as the controller.

PN-VPC Data Sheet TA200855 Issue 1/B 28/03/07