Installation Instructions

OCC/U ULTRASONIC OCCUPANCY DETECTION SYSTEM

OCC/U Ultrasonic Occupancy Detection System Installation Instructions TG101684 Issue 1/C 9/10/96

3

Digital Input

To other
detectors
(max 10)

Detector

Detector

Aux
Supply

IQ

Controller

24 Vdc
0 V

SIG

24 Vdc

0 V

SIG

24 Vdc

0 V

SIG

Digital Input

Voltage Input

To other
detectors
(max 10)

Detector

Detector

Voltage
Input

IQ

Controller

24 Vdc

0 V
SIG

24 Vdc

0 V

SIG

24 Vdc

0 V

SIG

INSTALLATION

(continued)

Electrical

(1)

Isolate the mains supply to IQ controller
and lighting at source before commencing
the electrical connections.

(2)

Wire the detector to the required IQ
Controller as shown below. Up to 10
detectors may be wired in parallel to a
single input channel.

Note that it is important to set the IQ Controller’s
input to digital (or voltage on an IQ70 series), see
the appropriate controller data sheet for details.

(3)

Wire the output of the IQ Controller to the
lighting relay/contactor.

Aux Supply

II_OCCU.PM6

28/11/96, 16:52

3