TREND DPSA User Manual

Dpsa, Technical specifications, Application

Advertising
background image

DPSA

DIFFERENTIAL PRESSURE SWITCHES

FOR AIR CONDITIONING / VENTILATION, USER-ADJUSTABLE

PRODUCT DATA AND INSTALLATION INSTRUCTIONS

TECHNICAL SPECIFICATIONS

Max. operating pressure 5000

Pa

Pressure media

air, non-flammable gases, and

non-aggressive

gases

Pressure connections

two plastic tubes, outside

diameter: 6.0 mm (0.24”)

Switching capacity

1.5 A, (0.4) /250 Vac

Electrical connections

screw terminals or AMP

connectors, 6.3 x 0.8,

DIN

46244

Conduit entry M20x1.5
Protection class IP

54

Mounting lugs

integrated in bottom housing

(alternative: mounting angles)

Medium/ambient temp.

-20...+85 °C (-4…+185 °F)

Storage temperature

-40...+85 °C (-40…+185 °F)

Membrane material silicone

APPLICATION

Differential pressure switches e.g. for monitoring filter, fan,
fire damper, or air flow status of air handling systems.

BENEFITS

Switching-point easily adjustable with scale in Pascal;

Direction of M20x1.5 conduit entry can be rotated in
steps of 120°;

Only one screw needed for housing cover.

APPROVALS

CE approval according to low-voltage directive EEC
73/23;

• Switch

according to VDE 0630;

EC Gas Appliance Directive 90/396/EEC according to
DIN EN 1854 (Nov. 01, 1997)

CONTENTS OF DELIVERY

The delivery includes (in the case of individual packages)
the following parts:

1 DPSA Differential Pressure Switch

1 Data Sheet with installation information

1 duct kit, consisting of:

-

2 m (2 yds 6”) of hosing

-

2 joining pipes with four screws

OPERATING RANGES

type

US code

adjustment range

for upper trip

pressure*

switching

difference

(hysteresis)

DPSA 200

882001720

20...200 (Pa)

10 (Pa)

DPSA 400

882001730

40...400 (Pa)

20 (Pa)

DPSA 1000

882001740

200...1000 (Pa)

100 (Pa)

*The trip pressure refers to vertical mounting. In case of
horizontal mounting (with the cover pointing upwards), the
range values increase by 20 Pa (i.e. a setting of 40 Pa will
switch at 60 Pa). The unit should not be mounted face
down.

DIMENSIONS

See "Mounting/Einbau/Montage" on page 4.

DPSA Data Sheet TA200878INT Issue 1/C 30/07/07

1

MU0B-0073GE51 R0707

Advertising