5

ABB

St375005

ODIN Meter

OD4110 connection via external current transformers,
3 phase meter

Article number

Type

Voltage (V)

Pulse output frequency

2CMA1310251000

OD4110

230/400V

1 imp./kWh

Technical Data

Voltage:

3x230/400 V AC

Voltage range

-20% to +15%

Max. current

10 A

Starting current

15 mA

Power consumption of current circuits

< 0.02 VA/phase

Power consumption of voltage circuits

< 2 VA/phase

Frequency

50/60 Hz

Accuracy of measurement

Class 2 (±2 %)

Standard

IEC 61036

Temperature range

-25 to +55

o

C

Programmable transformer ratios

5/5, 75/5, 100/5
150/5, 200/5, 250/5, 300/5,
400/5, 500/5, 600/5, 700/5
750/5, 800/5, 900/5 A/A

Material of front cover

Polycarbonate

Material of back cover

Polycarbonate/glass fibre

Resistance to heat and fire

Equivalent to IEC 695-2-1

Protection against penetration of dust and water

IP 20

Connection area in the current connection terminal

1 – 16 mm

2

Connection area in the voltage connection terminal

0.5 – 6 mm

2

Pulse output

Connection area in the connection terminal

0.5 – 2.5 mm

2

External pulse voltage

5 – 40 V DC

Max. current

100 mA

Pulse length

100 ms ±2.5 ms

Pulse frequency

1 imp/kWh

Standard

IEC 62053-1 (S0)

LED

Pulse frequency

1000 imp/kWh

Pulse length

40 ms

Display

LCD with 7 whole
number digits

Front view

Connection via current transformer

Type description

Load indicator

Pulse output
frequency

LED
frequency

National approval
symbol (SP)

Phase indicator

Identification No.

Adjustable transformer ratio

Wiring diagram

St375010