ABB
St375005
ODIN Meter
OD4110 connection via external current transformers,
3 phase meter
Article number
Type
Voltage (V)
Pulse output frequency
2CMA1310251000
OD4110
230/400V
1 imp./kWh
Technical Data
Voltage:
3x230/400 V AC
Voltage range
-20% to +15%
Max. current
10 A
Starting current
15 mA
Power consumption of current circuits
< 0.02 VA/phase
Power consumption of voltage circuits
< 2 VA/phase
Frequency
50/60 Hz
Accuracy of measurement
Class 2 (±2 %)
Standard
IEC 61036
Temperature range
-25 to +55
o
C
Programmable transformer ratios
5/5, 75/5, 100/5
150/5, 200/5, 250/5, 300/5,
400/5, 500/5, 600/5, 700/5
750/5, 800/5, 900/5 A/A
Material of front cover
Polycarbonate
Material of back cover
Polycarbonate/glass fibre
Resistance to heat and fire
Equivalent to IEC 695-2-1
Protection against penetration of dust and water
IP 20
Connection area in the current connection terminal
1 – 16 mm
2
Connection area in the voltage connection terminal
0.5 – 6 mm
2
Pulse output
Connection area in the connection terminal
0.5 – 2.5 mm
2
External pulse voltage
5 – 40 V DC
Max. current
100 mA
Pulse length
100 ms ±2.5 ms
Pulse frequency
1 imp/kWh
Standard
IEC 62053-1 (S0)
LED
Pulse frequency
1000 imp/kWh
Pulse length
40 ms
Display
LCD with 7 whole
number digits
Front view
Connection via current transformer
Type description
Load indicator
Pulse output
frequency
LED
frequency
National approval
symbol (SP)
Phase indicator
Identification No.
Adjustable transformer ratio
Wiring diagram
St375010