Check Current Loop Network

b

TX

a

RX

c

OK

IQ Faulty

Check network cabling for
short circuits with a
multimeter (NOT Megger)

Network Address Invalid

OK

OK

NBOX/EINC

Power up other nodes until
faulty node is found
(OK

). Correct fault.

(yellow)

(yellow)

(green)

0,2,3 or >119

Check baud rate

1.4 INSTALLATION - CONFIGURATION

(Continued)

14

Connect to EINC with IP Tool

SET Manual TE200147
IP Tool Manual TE200638

Router

EINC

Router

Either over Ethernet

or Local PC Ethernet Connection

SET v6
(including IP Tool)

XCITE/XA crossover adaptor
order separately (XCITE/XA/5
pack of 5)

SET v6
(including IP Tool)

Local PC (Ethernet) connection can be either to adjacent Ethernet
hub using standard cable only, or directly to EINC using standard
cable and crossover adaptor, XCITE/XA.

Initially access EINC via its MAC address

15

Configure Addressing Details with IPTool

EINC Data Sheet TA200137
IP Tool Manual TE200638

Parameter

Setting

Default

Function

Condition

Note

Address Module

IP Address

IP address
0.0.0.0 to 255.255.255.255

128.1.1.

<address switch>

Ethernet IP address

Last section set automatically

to address switch setting

1

Subnet Mask

Mask
0.0.0.0 to 255.255.255.255

255.255.
255.0

Mask applied to IP address to generate
subnet number

All EINCs on same channel
must be on same subnet to
create internetwork

1

UDP Port

0 to 65535

57612

Ethernet UDP port used by IQ system
equipment on Ethernet

All IQ system devices must

use same port to
intercommunicate

2

Router 1

IP address
0.0.0.0 to 255.255.255.255

0.0.0.0

IP address of router on same subnet as
EINC

MUST be set up for
communications outside own
subnet

3

Lan number

Lan number 1, 4 to 9, 11 to 119 20

Lan number of EINC on internetwork
<SET BY ADDRESS SWITCH>

4

Identifier

15 alphanumeric characters -
not /\({;?* characters

EINC

Identifier for EINC

Always set up for
supervisors/display panels

Advertising