1 installation - configuration, Check network, Configure alarm language – TREND NBOX(B)_PNC2 User Manual

Page 7: Check system, Close mbox

Advertising
background image

2 - 3

NBOX(B)/PNC2 Printer Node Controller Installation Instructions TG200266 Issue 1/C 21/07/04

Installation Instructions - Configuration

NBOX(B)/PNC2

O

I

NBOX(B)/PNC2

?

NBOX(B)/PNC2

?

2.1 Installation - Configuration

(continued)

T -

T +

R -

R +

L A N A

T -

T +

R -

R +

L A N A

T X

R X

O K

D T R B

D T R A

C T S B

C T S A

J1

3

J1

2

14

Check Network

(Lan A)

b

TX

a

RX

c

OK

PNC2 faulty

Check Network cabling for
short circuits with a
multimeter (NOT Megger)

Network Address invalid

0, 2, 3 or >119

OK

OK

NBOX(B)/PNC2

Check baud rate

Power up other nodes until
faulty node is found

(OK

). Correct fault.

(yellow)

(yellow)

(green)

PNC2

15

Configure Alarm Language

The PNC2 will automatically set its alarm language to that of the other nodes on the local Lan if possible (otherwise stays in English). It may be changed
if required:

Note that if the PNC2 is reset by power up or on change of address or baud rate, the PNC2 will automatically set its language

Recommend use of PowerTool
or Wupdn

if required

Set language by R(P=x)
where x defines language as follows:
x=0 English, =1 Spanish, =2 Finnish, =3 Swedish, =4 Norwegian, =5 Danish, =6 German, =7 Italian, =8 Portuguese, =9 French.

IQ Configuration Manual 90-1533
PNC2 Data Sheet TA200263
PowerTool Manual TE200163
Wupdn Manual TE200162

16

Check System

PNC2

IQ

! alarm

! alarm

17

Close MBOX

if fitted in ENCLS/MBOX/IQ22x

a

b

Lan