IQView../RPM Installation Instructions TG200712 Issue 1/F 10/01/07

Installation Instructions

IQView../RPM

3.1 Installation - Mounting

(continued)

Load on when
Alarm not present,
(Relay off)

Relay Output Arc Suppression
Installation Instructions TG200208

11

3 2 1

1

LINK

RS232

Rx Tx

OK

28-36 V
24 V

ETHERNET

OK

DATA

R+ R- T+ T-
7 6 5 4

AC rating: 62.5 VA

e.g 40 Vac max @ 1.5 A, 24 Vac @ 2.5 A

DC rating: 60 W

e.g. 40 Vdc max @ 1.5 A, 24 Vdc @ 2.5 A

Note that UL rating applies up to 30 V maximum

Connect Relay Output

Arc suppression
r e c o m m e n d e d

WARNING:

The wires may be connected to
hazardous voltages. Disconnect
power before attampting any wiring.

Load on when
Alarm present,
(Relay energised)

3
2

1

power

load

3

2

1

power

load

3 2 1

1

rear view
of connector

Note that the relay output alarm action must be enabled (it is disabled by default), see 2.2 step 15.

if required (for alarm notification)