Thermal specifications, General specifications, Output specifications – TREND RN User Manual

Page 9: Input specifications

Advertising
background image

2

Specifications are subject to change without notice (30.09.2005)

Thermal Specifications

RN.F..30

RN.F..50

Operational temperature

-20° to +70°C (-4° to +158°F)

-20° to +70°C (-4° to +158°F)

Storage temperature

-20° to +100°C (-4° to +212°F)

-20° to +100°C (-4° to +212°F)

Junction temperature

< 125°C (257°F)

< 125°C (257°F)

R

th

junction to ambient (AC load)

2.8 K/W

1.7 K/W

General Specifications

RN.F12...

RN.F23...

RN.F48...

Operational voltage range

85 to 140 VAC

85 to 265 VAC

190 to 530 VAC

Non-rep. peak voltage

800 V

p

800 V

p

1000 V

p

Varistor voltage

275 VAC

275 VAC

510 VAC

Zero voltage turn-on

< 10 V

< 10 V

< 20 V

Operational frequency range

45 to 65 Hz

45 to 65 Hz

45 to 65 Hz

Power factor at rated voltage

0.9

0.9

0.9

Average output power

0 to 100%

0 to 100%

0 to 100%

Output power resolution

1/64 of 100%

1/64 of 100%

1/64 of 100%

Approvals

UL, cUL, CSA

UL, cUL, CSA

UL, cUL, CSA

CE-marking

Yes

Yes

Yes

Norms fulfilled

EN 60947-1 Low-voltage switchgear and control gear. Part 1- General Rules.
EN 61000-6-1 Generic Immunity Standard. Residential, Commercial & Light Industry Environment
EN 61000-6-2 Generic Immunity Standard. Industrial Environment

Output Specifications

RN.F..30

RN.F..50

Rated operational current

RN1F..

AC51

@Ta=30°C

30 A

50 A

@Ta=40°C

30 A

50 A

@Ta=50°C

23 A

38 A

@Ta=60°C

20 A

30 A

RN2F..

AC51

@Ta=30°C

30 A total sum (2 x 15A)

50 A total sum (2 x 25A)

@Ta=40°C

30 A total sum (2 x 15A)

50 A total sum (2 x 25A)

@Ta=50°C

23 A total sum (2 x 11.5A)

38 A total sum (2 x 19A)

@Ta=60°C

20 A total sum (2 x 10A)

30 A total sum (2 x 15A)

Zero crossing detection

Yes

Yes

Min. operational current (per pole)

500 mA

500 mA

Rep. overload current t=1 s

(Tj init.=25°C)

55 A (rms)

125 A (rms)

Non-rep. surge current t=10 ms

(Tj init.=25°C)

< 300 A

p

< 580 A

p

Off-state leakage current,
@ rated voltage and frequency

(Tj.=125°C, max.)

< 6 mA

< 6 mA

I

2

t for fusing t=1 to 10 ms

450 A

2

s

1680 A

2

s

Critical dV/dt off-state

500 V/µs

500 V/µs

RN 1F

Input Specifications

RN.F..I..

Current controlled input

Control current range

4 - 20 mA

Allowable input current

50 mA

Reverse polarity protected

Yes

Voltage drop

10 VDC @ 20 mA

RN.F..V..

Voltage controlled input

Supply voltage range

21 - 27 VAC, 12 - 32 VDC

Supply current

30 mA @ 24 VAC/32 VDC

Control voltage range

0 - 10 V

Control input current

0.1 mA @ 10 VDC

Advertising
This manual is related to the following products: