Model ct-7500 operating instructions – Vanguard CT-7500 User Manual

Page 48

Advertising
background image

MODEL CT-7500

OPERATING INSTRUCTIONS

42

Rev 2 Jan 2001

9.8 Recall a Breaker Test Plan

A breaker test plan contains breaker maximum/minimum operating parameters. A typical list of

operating parameters is shown as follows:

„

Max/Min Contact/Resistor Trip Time.

„

Max/Min Contact/Resistor Close Time.

„

Max Contact Spread Time.

„

Max Resistor Contact Spread Time.

„

Max/Min Stroke.

„

Max/Min Trip Velocity.

„

Max/Min Close Velocity.

„

Max/Min Over Travel.

„

Max/Min Bounce Back.

„

Trip Analysis Points.

„

Close Analysis Points.

By recalling a Test Plan before testing, a user doesn't have to set analysis points to calculate

the Trip or Close velocity of the circuit-breaker contacts. Since a Test Plan contains other breaker
test parameters, the test report also displays a Pass/Fail status for each parameter tested.

Table 9-10. Recalling a Test Plan

STEP

OPERATION

ACTION

DISPLAY

1

SELECT SET UP MENU.

PRESS #3 KEY.

1. ANALYSIS POINTS
2. MEASUREMENT UNIT
3. SAVE / RESTORE
4. NEXT PAGE

2

SELECT ANALYSIS MENU.

PRES # 1 KEY.

1. OPEN TIMING
2. CLOSE TIMING
3. PRINT SETTING
4. TEST PLANS

3

SELECT TEST PLANS.

PRESS # 4 KEY.

1. LOAD TEST PLAN
2. PRINT TEST PLAN
3. PRINT DIRECTORY

4

SELECT LOAD TEST PLAN.

PRESS # 1 KEY.

LOAD TEST PLAN
"UP" TO SCROLL
"ENTER" TO SELECT

5

VIEW TEST PLAN HEADER.

PRESS UP ARROW
KEY TO SCROLL.

DISPLAY TEST PLAN HEADER

6

CONFIRM TEST PLAN TO BE
LOADED.

PRESS "ENTER"
KEY.

1. TEST BRKR
2. GET RSLT
3. SET UP
4. DIAGNOSTIC